MJ-X
L
Communications Module
13
9.
If you are installing the RS-232/485 version of the communications module, plug the power connector into
J411 on the MJ-X Power Board as shown in Figure 5-6.
Processor Board
Power Board
Connector J411
Connector J105
Txd
Rxd
GND
RTN
Data
Rxd
Txd
CTS
RTS
POWER
Wdog
Comm
Membrane Switch Cable
Figure 5-6 MJ-X Communications Module Cable Routing
10.
Feed the PDS cable through the PDS strain relief opening in the rear cover.
11.
Reinstall the rear cover of the control panel, attaching it using the six screws.
12.
Rotate the PDS strain relief plate to the closed position and tighten the screws for the strain relief plate.
13.
Follow the procedure in section 6 Testing on page 14 to test the communications module.