Properties
1.1 Power module PM-E DC24..48V/AC24..230V (6ES7138-4CB11-0AB0)
Power module PM-E DC24..48V/AC24..230V (6ES7138-4CB11-0AB0)
8
Manual, 04/2007, A5E01120024-01
Maximum configuration per voltage group
The number of modules that can be connected depends on the total current of all modules in
a voltage group. This total must not exceed the maximum current carrying capacity.
Address space of inputs/outputs
Address space of inputs/outputs by selecting the following as an option:
Options
Address space of the inputs Address space of the outputs
Status byte (S)
1 byte
--
Option handling (O)
8 bytes
8 bytes
Status byte and option handling (SO) 9-byte inputs
9 bytes (9th byte not relevant)
General terminal assignment
Note
Terminals A4 and A8 are only available at specified terminal modules.
Terminal assignment PM-E DC24..48V/AC24..230V (6ES7138-4CB11-0AB0)
Terminal Assignment Terminal Assignment
Notes
2
L+/L1
6
L+/L1
3
M/ N
7
M/ N
A4
AUX1
A8
AUX1
•
L+/L1: Rated load voltage 24 VDC to 48 VDC
•
M: Chassis ground
•
N: Neutral conductor
•
AUX1: Protective-conductor terminal or potential bus (freely usable
up to 230 VAC)