Installation Instructions

11-A-1193-01 Rev. 00

-3-

-2-

DANGER

Hazardous voltage.

Will cause death or

serious injury.

Keep out.

Qualified personnel only.

Disconnect and lock off all

power before working on 

this equipment.

9.  Torque all connections to the values specified on

     the Hardware Tightening Torque label affixed to

     the rear of the deadfront.

5.  Position the breaker barrier assembly (Item 1) at the

     MAIN END of the panel.  (See Fig. 1)  Ensure the

     straps are properly snapped into the barrier and then

     align them with the panel bus.  Secure the straps to

     the phase bus with 1/4”-20 SEMS screws (Item 5).

     Do not tighten at this time.

8.  On 1-phase 3-wire and 3-phase 4-wire systems the

     neutral lug assembly (Item 4) is required.  The 

     neutral lug assembly arrives in the kit ready to

     assemble at any open corner.  Locate the neutral

     lug assembly at the corner closest to where the

     cables will terminate into the breaker.  Install by

     positioning it below the neutral cross bus or the

     neutral lug pad, inserting the exposed stud through

     the appropriate hole and securing with the 1/4”-20

     belleville washer nut (part of Item 4).

The following instructions are for the installation of a Siemens main/subfeed breaker kit for Type 

BL

BQD

xGB 

or

 3VA4

 

breakers in Revised P1 Panelboards.  The kit may be installed as a main or a subfeed in panels rated 250 amps or less.  

For Revised P1 400A panels, it may be installed in subfeed applications ONLY (see Fig. 4).  The parts provided in this kit 

are for connection to a 1-phase 2 or 3-wire system in kit 

MBKVA41A

 or for connection to a 3-phase 3 or 4-wire system in 

kit 

MBKVA41B

.  The breaker is 

NOT

 included with this kit and must be purchased separately.  Be sure to choose the appro-

priate breaker for the system in use.  For systems with no neutrals, disregard the neutral connection.

6.  Secure the breaker barrier assembly to the base

     rails with two #10-24 screws (Item 6).  Do not

     tighten at this time.

4.  Prepare the kit based on the breaker type:

     

BL

/

BQD

 breaker:  Position the breaker support

     bracket (Item 8) onto the breaker barrier assembly

     (Item 1) by swinging the hooks on the bottom of the

     bracket into the proper holes on the breaker barrier

     assembly.  (See Fig. 2 & 3)  Complete assembly by

     inserting a 1/4”-20 screw (Item 5).  Torque to 40 lb-in.

     

xGB

/

3VA4

 breaker:  Proceed to Step 5.  

10. Attach the main cables to the breaker and neutral

      terminal and torque connections to values specified

      on the device.  If no values are listed on the device, 

      refer to the Hardware Tightening Torque label 

      affixed to the rear of the deadfront.

11.  Remove the blank filler or escutcheon installed

       on any deadfront opening in the area that will

       cover this kit.  Install the escutcheon (Item 2)

       provided with this kit into the front of the

       deadfront as shown.  (This escutcheon has

       a rib on the rear whose orientation should be

       towards the unit space for proper fit.)

       NOTE:  If installing a 2-pole breaker, use the

       blank filler (Item 9) by inserting it into the 

       open spot on the breaker escutcheon (Item 2).

7.  Assemble the breaker (

purchased separately

) onto

     the breaker barrier assembly and secure it using the

     #10-32 x 3/8” SEMS screws (Item 7).

12.  For main breaker applications, apply the

       “MAIN” label (Item 3) to the breaker escutcheon

       as shown.

13.

  Before energizing the panel, ensure that all

       connections have been properly torqued,

       the deadfront is installed and all fillers are

       in place.

14.  Follow Steps 1 through 11, except that the kit

       must be installed at the feed-thru or subfeed end

       of the panel and any pre-existing assembly at

       that location must be removed prior to installation

       of this kit.  In addition, do NOT install the “MAIN”

       label (skip Step 12).  

Finish with Step 13.

For installation as a main breaker:

For installation as a subfeed breaker:

(For panels with feed-thru or subfeed space ONLY)

1.  

Lock off all power supplying this 

     equipment before working on it.

3.  Remove the lugs (if installed).

2.  Remove the deadfront.

(For 250A panels ONLY)

MAIN

END

FEED-THRU

OR SUBFEED

END

P1-400 PANELBOARD WITH SUBFEED BREAKER

STRAP AND BARRIER ASSEMBLY

1

BREAKER ESCUTCHEON

MAIN LABEL

NEUTRAL LUG ASSEMBLY

1/4”-20 x 1/2” HEX HEAD SEMS* ASSEMBLY SCREW

#10-24 x 7/16” SLOTTED HEX WASHER THREAD-FORMING SCREW

** (2) for 1Ø, (3) for 3Ø

1

***

2

1

1

1

2

3

4

5

6

7

#10-32 x 3/8” HEX HEAD SEMS* ASSEMBLY SCREW

**

8

9

* SEMS assembly screws have a captive washer on the screw

THIS KIT CONTAINS THE FOLLOWING ITEMS:

ITEM

QTY

DESCRIPTION

N/A

N/A

30 lb-in

N/A

N/A

TORQUE

lb-in

20 lb-in

1

BL / BQD BREAKER SUPPORT BRACKET

N/A

1

1” BLANK FILLER

N/A

3-PHASE

P1-250

*** (3) for 1Ø, (4) for 3Ø

**** 72 lb-in for Strap to Bus connections; but ONLY 40 lb-in for plastic breaker bracket to plastic barrier connection

****

(3VA4 shown)

DEADFRONT

MAIN

END

FEED-THRU

OR

SUBFEED

END

3

1

9

5

2

5

DEADFRONT

SUPPORT

BASE

RAIL

NEUTRAL

LUG PAD

NEUTRAL

CROSS BUS

6

7

4

Breaker Support Bracket

assembled to

Strap and Barrier Assembly

How to

Assemble

Fig. 1

Fig. 2

Fig. 3

Fig. 4

8

1

5

BARRIER HOOK HOLES

BRACKET

HOOKS