Error
code
Diagnostic
code
Device
Display
Meaning for the LMV5 system
Troubleshooting
B7 13 O2M
No valid COx signal from PLL52
Compensation element voltage outside
the valid range
Check connections (polarity, short-circuit, open-circuit).
Check housing temperature of the QGO (temperature inside -
25...120 °C)
B7 15 O2M
No valid COx signal from PLL52
Temperature of combustion air sensor
outside the valid range (-20...+800 °C)
Check the connection (correct polarity, short-circuit)
Check ambient temperature
B7 16 O2M
No valid COx signal from PLL52
Temperature of flue gas sensor outside
the valid range (-20...+800 °C)
Check the connection (correct polarity, short-circuit)
Check ambient temperature
B7 17 O2M
No valid COx signal from PLL52
Fault during combustion air sensor test
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 18 O2M
No valid COx signal from PLL52
Fault during thermo couple
test
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 19 O2M
No valid COx signal from PLL52
Fault during compensation element test
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 1A O2M
No valid COx signal from PLL52
Fault during channel comparison of O2
signal
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 1B O2M
No valid COx signal from PLL52
Fault ADC test voltages
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 20 O2M
No valid COx signal from PLL52
Temperature of QGO measuring cell too
low
Check mains power supply on O2 module.
Check fuse F2 on O2 module.
Check connection between O2 module and QGO heating
B7 21 O2M
No valid COx signal from PLL52
Temperature of QGO measuring cell too
high
Check QGO temperature
B7 22 O2M
No valid COx signal from PLL52
Fault during calculation test
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module
B7 23 O2M
No valid COx signal from PLL52
Measured internal resistance of the QGO
measuring cell is smaller than 5 Ohm or
greater than 150 Ohm
Check the connection (correct polarity, short-circuit)
If fault occurs after more than 1 year, QGO may have reached
the end of its service life
Replace QGO
B7 24 O2M
No valid COx signal from PLL52
Measured response time of the QGO
measuring cell exceeds 5 seconds
Check mounting position of QGO.
Check to see if QGO is dirty.
If fault occurs after more than 1 year, QGO may have reached
the end of its service life
Replace QGO
B7 25 O2M
No valid COx signal from PLL52
Fault occurred during O2 sensor test
Check fluctuations of the O2 value
B7 30 O2M
No valid COx signal from PLL52
CAN fault
If fault occurs sporadically: Improve EMC.
If fault occurs constantly: Replace the defective O2 module