CC1N7130en
22.08.2013

Building Technologies Division

Infrastructure & Cities Sector

7

130

Oil Burner Controls

LMO14...
LMO24...
LMO44...

Microcontroller-based oil burner controls for the startup, supervision and control 
of forced draft oil burners in intermittent operation. Standard versions with an oil 
throughput up to 30 kg / h, special versions above 30 kg / h.

The  LMO14...,  LMO24...,  LMO44...  and  this  Data  Sheet  are  intended  for  use  by 
OEMs which integrate the burner controls in their products.

Use, features

The LMO... are designed for the startup and supervision of 1- or 2-stage forced draft oil 
burners  in  intermittent  operation.  Yellow-burning  flames  are  supervised  with  photo 
resistive detectors QRB..., blue-burning flames with blue-flame detectors QRC...
In terms of housing dimensions, electrical connections and flame detectors, the LMO... 
are identical with the LOA... oil burner controls.

-

Oil burners with fans to EN 267

-

Burner  controls  for  use  with  atomization  oil  burners  of  monoblock  design  to 
DIN EN 230:2005-10

-

LMO44... for use with stationary direct-fired air heaters

-

Undervoltage detection

-

Electrical remote reset

-

Bridging contact for oil preheater 

-

Monitoring of time for oil preheater 

-

Accurate and reproducible control sequence thanks to digital signal handling

-

Controlled intermittent operation after 24 hours of continuous operation

-

Limitation of the number of repetitions

-

Multicolor indication of fault status and operational status messages

Use

General features

Distribuitor: FLAME POWER SRL 021-3121727 ; 0744-340566 [email protected] ; www.arzatoare.ro

Содержание LMO14 Series

Страница 1: ...detectors QRB blue burning flames with blue flame detectors QRC In terms of housing dimensions electrical connections and flame detectors the LMO are identical with the LOA oil burner controls Oil burners with fans to EN 267 Burner controls for use with atomization oil burners of monoblock design to DIN EN 230 2005 10 LMO44 for use with stationary direct fired air heaters Undervoltage detection El...

Страница 2: ...ere is a risk of impairment of safety functions and of electric shock hazard x Fall or shock can adversely affect the safety functions Such units must not be put into operation even if they do not exhibit any damage If not observed there is a risk of impairment of safety functions and of electric shock hazard x When replacing LOA26 or LOA36 any ARK21 remote lockout reset module or similar modules ...

Страница 3: ...O44 F M L L X N to WLE Service notes x Use the KF8885 KF8833 KF8840 service adapters for short periods of time only Life cycle Burner controls has a designed lifetime of 250 000 burner startup cycles which under normal operating conditions in heating mode correspond to approx 10 years of usage starting from the production date given on the type field This lifetime is based on the endurance tests i...

Страница 4: ...A max t3 min t3n max t4 min Standard versions LMO14 111C2 AC 230 V 1 30 kg h x x 2 5 s 15 16 s 10 s 15 s 10 s LOA24 171B27 LOA26 171B27 LOA36 171A27 LMO14 113C2 AC 230 V 1 30 kg h x x 2 5 s 15 16 s 10 s 15 s 3 s LOA24 173A27 LMO24 111C2 AC 230 V 2 30 kg h x x 2 5 s 15 16 s 10 s 15 s 10 s 15 s LOA24 171B27 LOA26 171B27 LOA36 171A27 LMO24 111C1 AC 120 V 2 30 kg h x x 2 5 s 15 16 s 10 s 15 s 10 s 15 ...

Страница 5: ... burner controls Demo case KF8891 refer to User Manual B7989 For demonstrating the functions of burner controls Test adapter KF8885 refer to Operating Instructions B7986 For checking the functions of burner controls on the burner With switch for manual startup of the burner With switch for simulating the oil preheater s release contact With 2 pairs of jacks for measuring the flame detector current...

Страница 6: ...Max 5 A Terminals 3 and 8 Max 3 A Max 3 A Max 3 A Terminals 4 and 5 Max 1 A Max 1 A Max 1 A Terminal 6 Max 1 A Max 2 A Max 2 A Terminal 10 Max 1 A Max 1 A Max 1 A Storage DIN EN 60721 3 1 Climatic conditions Class 1K3 Mechanical conditions Class 1M2 Temperature range 20 60 C Humidity 95 r h Transport DIN EN 60721 3 2 Climatic conditions Class 2K2 Mechanical conditions Class 2M2 Temperature range 2...

Страница 7: ...µA QRC 45 µA 45 µA The values given in the table above only apply under the following conditions Mains voltage depending on execution AC 120 V or AC 230 V Ambient temperature 23 C QRB QRC 12 11 LMO bl µA DC QRB 7130v01 0700 sw 12 11 LMO 1 sw bl br µA DC QRC1 7130v02 0700 Legend µA DC DC microammeter with an internal resistance of Ri max 5 k bl Blue sw Black br Brown As an alternative to detector c...

Страница 8: ...restart Extraneous light during prepurge time t1 5 s before fuel valve BV1 release Lockout at the end of prepurge time t1 Extraneous light during waiting time tw Prevention of startup lockout after 40 seconds at the latest No flame at the end of safety time TSA Lockout at the end of safety time TSA blink code 2 Loss of flame during operation Max 3 repetitions followed by lockout Oil preheater s re...

Страница 9: ...erface OCI400 and PC software ACS400 ACS410 or flue gas analyzers of different makes Visual diagnostics In normal operation the different operating states are indicated in the form of color codes according to the color code table given below During startup status indication takes place according to the following table Color code table for multicolor signal lamp LED Status Color code Color Waiting ...

Страница 10: ...rror code table EK 3 s Interface diagnostics PC analyzer OCI400 EK 3 s 7130z04e 0602 Reset On Visual diagnostics Lockout position Lockout position Lockout position Error code table Red blink code of signal lamp LED Alarm AL at term 10 Possible cause 2 blinks On No establishment of flame at the end of safety time TSA Faulty or soiled fuel valves Faulty or soiled flame detector Poor adjustment of bu...

Страница 11: ... internal diagram LMO24 Control sequence LMO24 1 2 6 7 4 5 10 11 12 W SB R L N M Z BV1 AL Si 8 3 OW OH N 8 3 QRB QRC br bl sw 1 7130a04e 0908 9 EK2 EK1 µC control K1 K2 K4 BV2 LED kbr FSV µC2 µC1 K3 R W SB OH OW M Z BV2 FS A A B C D 1 8 3 3 6 5 11 12 t1 t3 t3n TSA tw Only with LMO24 113C2 re ignition BV1 4 t4 t1 Z FS 6 11 12 7130d03e 1207 t3n t3n Connection diagram and internal diagram LMO44 Contr...

Страница 12: ...sw black R Control thermostat or pressurestat SB Safety limit thermostat Si External primary fuse W Limit thermostat or pressure switch Z Ignition transformer TSA Ignition safety time tw Waiting time t1 Prepurge time t1 Purge time t3 Preignition time t3n Postignition time t4 Interval from flame signal to release of fuel valve 2 BV2 A Start of startup sequence with burners using an oil preheater OH...

Страница 13: ...30m04 1004 22 9 7130m05 0904 7 44 L Type reference Length L in mm AGK20 19 19 AGK20 43 43 AGK20 55 55 LMO LMO with extension of lockout reset button AGK20 2013 Siemens AG Infrastructure Cities Sector Building Technologies Subject to change Plug in base AGK11 Distribuitor FLAME POWER SRL 021 3121727 0744 340566 contact arzatoare ro www arzatoare ro ...

Отзывы: