8/15
Building Technologies Division
CC1N7418en
21.06.2016
Technical data
Mains voltage
- Only with LGA63...
AC 220 V
15 %...AC 240 V +10 %
AC 100 V –15 %...AC 110 V +10 %
AC 230 ±10 %
Mains frequency
50...60 Hz ±6 %
Power consumption
3 VA
Perm. mounting position
Optional
Degree of protection
IP40 (when integrated)
Safety class
I (burner control with plug-in base)
Input current at terminal 1
Max. 5 A
Permissible cable lengths
Detector cable, laid separately
Max. 3 m with 100 pF/m line capacitance
Perm. electrical rating
- Terminal 4
Max. 4 A
- Terminal 5
Max. 1 A
- Terminal 6
Max. 2 A
- Terminal 7
Max. 2 A
- Terminal 8
Max. 4 A
- Terminal 9
Max. 0,1 A
- Terminal 10
Max. 1 A
Cable length terminal
20 m at 100 pF/m
Weight
Approx. 180 g
Storage
DIN EN 60721-3-1
Climatic conditions
Class 1K3
Mechanical conditions
Class 1M2
Temperature range
-20...+60 °C
Humidity
<95 % r.h.
Transport
DIN EN 60721-3-2
Climatic conditions
Class 2K2
Mechanical conditions
Class 2M2
Temperature range
-50...+60 °C
Humidity
<95 % r.h.
Operation
DIN EN 60721-3-3
Climatic conditions
Class 3K5
Mechanical conditions
Class 3M2
Temperature range
0...+60 °C
For LGA41.173A27 and LGA52.171B27:
-20...+60 °C
Humidity
<95 % r.h.
Installation altitude
Max. 2,000 m above sea level
Caution!
Condensation, formation of ice and ingress of water are not permitted!
If this is not observed, there is a risk of loss of safety functions and a risk of
electric shock.
General unit data
Environmental
conditions