7/25
Building Technologies Division
CC1N7451en
20.11.2017
Type summary
The type references given below apply to the LFL without plug-in base and without
flame detector. For ordering information for plug-in bases and other accessories, see
Accessories
.
Switching times are given in seconds, in the burner startup sequence, valid for 50 Hz
mains frequency. At 60 Hz, switching times are about 17 % shorter.
The type references apply to burner controls operating on AC 230 V, 50...60 Hz.
Flash steam
generators
Flash steam
generators
Incl.
stationary
air heaters
²)
Large
atmospheric
burners
Type
LFL1.122 ¹)
02 series
LFL1.133 ¹)
02 series
LFL1.322 ¹)
02 series
LFL1.333 ¹)
02 series
LFL1.335 ¹)
01 series
LFL1.622 ¹)
02 series
LFL1.635 ¹)
01 series
LFL1.638
01 series
Article
no.
BPZ:LFL1.122
BPZ:LFL1.133 BPZ:LFL1.322
BPZ:LFL1.333
BPZ:LFL1.335
BPZ:LFL1.622
BPZ:LFL1.635
BPZ:LFL1.638
Times in seconds (s)
t1
10
9
36
31
37
65
66
66
TSA
2
3
2
3
2.5
2
2.5
2.5
TSA´
2
3
2
3
5
2
5
5
t3
4
3
4
6
5
4
5
5
t3´
4
---
4
6
2.5
4
2.5
2.5
t4
6
6
10
11.5
12.5
10
12.5
12.5
t4´
6
---
10
11.5
15
10
15
15
t5
4
3
10
11.5
12.5
10
12.5
12.5
t6
10
14.5
12
18
15
12
15
15
t7
2
3
2
3
2.5
2
2.5
2.5
t8
30
29
65
69
74
95
103
103
t9
2
3
2
3
5
2
5
7.5
t10
6
6
8
11.5
10
8
10
10
t11
Optional
t12
Optional
t13
10
14.5
12
17
15
12
15
15
t16
4
3
4
6
5
4
5
5
t20
32
60
---
26
22
---
---
---
¹) Available as AC 100...110 V versions; add type suffix «-110 V» when ordering
²) Reversed polarity protection conforming to Dutch installation standard: AGM30
Legend of times
TSA
Ignition safety time
t8
Duration of startup sequence (without «t11» and «t12»)
TSA‘
Ignition safety time or first safety time
t9
Second safety time with burners using pilot burners
(startup with burners using pilot burners)
t10
Interval from start to the beginning of the air pressure
t1
Prepurge time with air damper open
check, excluding running time of air damper
t3
Preignition time
t11
Air damper running time to the OPEN position
t3‘
Preignition time (long)
t12
Air damper running time to the low-fire position MIN
t4
Interval between voltage at terminals 18 and 19
t13
Permissible afterburn time
t4‘
Interval between start of TSA´ and release of valve at
t16
Interval until OPEN command for the air damper is given
terminal 19
t20
Interval to the self-shutdown of the sequence switch
t5
Interval between power at terminals 19 and 20
after startup
t6
Postpurge time (with «M2»)
t7
Interval between start command and power at terminal 7
(start delay for «M2»)