Note:

Before testing, you MUST notify the
personnel in charge of the Fire Alarm
panel, since the test may disrupt normal
business operations. In addition, you
MUST notify the local Fire Department if
the department is connected to the
municipal tie.

Alarm Operation

Test the annunciator for alarm operation by:

  • Activating an initiating device on a zone

configured for alarm.

  • Confirming the normal alarm functioning of

the unit and the Control Panel.

The ALARM LED (LED on left) should glow red
for the appropriate zone.

Supervisory Operation

Test the annunciator for supervisory operation by:

  • Activating an initiating device on a zone

configured for supervisory.

  • Confirming the normal supervisory functioning

of the unit and the Control Panel.

The SUPERVISORY LED (LED on left) should
glow yellow for the appropriate zone.

Trouble Operation

Test the annunciator for trouble operation by:

  • Disconnecting a wire from a zone at the

Control Panel.

  • Confirming the normal trouble functioning of

the unit and the Control Panel.

The TROUBLE LED (LED on right) for the
appropriate zone should glow yellow.

Annunciator Supervision

Check annunciator supervision by:

  • Disconnecting the DATA line from TB1 on

the module.

  • The Control Panel indicates the trouble, but

if there are two annunciators on the system,
it does not tell which of the two is in trouble.

For more information on this supervision, see
the section on 

Troubleshooting on page 4.

4.

Press the RESET key nine times to select
program level 9 to program the LED-3/4.
Then press the SILENCE key to select
program level 9.

Program level 9 has only one sublevel:

 

Enable/Disable SRC-8 and LED-3/4

The sublevel is displayed on the seven segment
display following the hyphen (-).  To select the
desired sublevel, press the SILENCE key as
required. Select the device according to the table
below:

IDC Zone 1 LED

SRC-8*

IDC Zone 2 LED

LED-3/4 No. 1

IDC Zone 3 LED

LED-3/4 No. 2

(IDC = Initiating Device Circuit)

To enable/disable the LED-3/4:

1.

Press the RESET key to advance the IDC
TROUBLE LED to the desired device.

2.

Press the DRILL key to enable or disable the
device.

3.

The ALARM LED indicates the enable/
disable status:

If the LED is ON, the LED-3/4
is enabled.

Exiting the Program Mode

To exit the Program mode:

1.

Press the ACK key until the PROGRAM/
TEST LED turns off.

2.

Continue to press ACK until the letter

 L

appears on the seven segment display.

3.

Then press the SILENCE key to exit.

MAINTENANCE AND TESTING

No periodic maintenance is required; however,
Siemens Building Technologies, Inc. recom-
mends periodic testing.

* See SXL-EX Manual, P/N 315-095997, for

details.

Содержание LED-3

Страница 1: ...s of the annunciator when troubleshooting the installation TABLE 1 ELECTRICAL OPERATING CHARACTERISTICS Input Power 24 VDC no LEDs on 10mA Output Power 2mA per ALARM SUPERVISORY TROUBLE LED 42mA max all LEDs on Remove all system power before installation first battery and then AC To power up connect AC first then the battery BACK FRONT INSTALLATION GUIDELINES Install in accordance with NFPA 72 NEC...

Страница 2: ...ort TB 3 Power Limited Style 4 Supervised Positive and Negative Ground Fault Detected at 20K for Terminals on TB 1 3 After the system is tested tighten the mount ing screws 4 Fill in the appropriate information for each zone on the card provided PROGRAMMING THE SXL EX SYSTEM FOR THE LED 3 4 MODULE Enabling the Program Mode Enter level 9 of the programming mode 1 Press the RESET and DRILL keys at t...

Страница 3: ...dule The Control Panel indicates the trouble but if there are two annunciators on the system it does not tell which of the two is in trouble For more information on this supervision see the section on Troubleshooting on page 4 4 Press the RESET key nine times to select program level 9 to program the LED 3 4 Then press the SILENCE key to select program level 9 Program level 9 has only one sublevel ...

Страница 4: ...Test Mode To exit the test mode first press the ACK key until the PROGRAM TEST LED turns off and the letter L appears on the seven segment display Then press the SILENCE key BATTERY CALCULATIONS Battery backup is required for the LED 3 4 To determine the size battery you need use the battery calculation table in the SXL EX Manual P N 315 095997 TROUBLESHOOTING If an LED fails to respond 1 Check DS...

Отзывы: