Siemens KNX RDF600KN Скачать руководство пользователя страница 18

18 / 18

Siemens

RDF600KN, RDF600KN/VB, RDF600KN/S

A6V11425204_en--_d

Smart Infrastructure

Semi flush-mount communicating room thermostats

2020-02-21

Issued by
Siemens Switzerland Ltd
Smart Infrastructure
Global Headquarters
Theilerstrasse 1a
CH-6300 Zug
Tel. +41 58 724 2424
www

© Siemens Switzerland Ltd, 2019

Technical specifications and availability subject to change without notice.

www.siemens.com/buildingtechnologies

Dimensions

Dimensions in mm

86

8

6

3

076

M0

1

30

16

3

0

7

6

M

1

2

80

3

0

7

6

M

1

3

_

0

1

Содержание KNX RDF600KN

Страница 1: ...for keycard contact external sensor etc Operating modes Comfort Economy and Protection Automatic or manual fan speed control Automatic or manual heating cooling changeover Minimum and maximum limitation of room temperature setpoint Control depending on the room or the return air temperature Adjustable commissioning and control parameters Commissioning with Synco ACS ETS or via local HMI Integratio...

Страница 2: ...nt Compressors in DX type equipment with electric heater The thermostats control One 1 speed or 3 speed fan One or two on off valve actuators One on off valve actuator and one 1 stage electric heater One 3 position valve actuator One 1 stage compressor in DX type equipment or one 1 stage compressor with electric heater Used in systems with Heating or cooling mode Automatic heating cooling changeov...

Страница 3: ...xternal room temperature or return air temperature sensor Dew point sensor Electric heater enable Fault input Monitor input for temperature sensor or switch state Window contact Presence detector standard presence and hotel presence Advanced fan control function e g fan kick fan start selectable fan operation enable disable or depending on heating or cooling mode Purge function together with 2 por...

Страница 4: ...e following applications which can be configured using the DIP switches on the inner side of the thermostat s front panel or a commissio ning tool All DIP switches need to be set to OFF remote configuration factory setting to select an application via commissioning tool Remote configuration via commissioning tool factory set Synco ACS ETS DIP switches 1 ON 2 3 Remote configuration ...

Страница 5: ...ter heating or cooling ON OFF 1 ON 2 3 3076D20 B1 M1 Y1 T B2 T T B1 Y1 M1 3171D21 T B2 YE T B1 T B1 2 pipe fan coil unit 3 position heating or cooling 1 ON 2 3 4 pipe fan coil unit ON OFF heating and cooling 1 ON 2 3 3076D20 B1 M1 Y1 T B2 T T B1 T Y2 Y1 M1 3076D22 B1 T B1 Y1 Heating or heating cooling valve actuator B1 Return air temperature sensor or external room temperature sensor optional Y2 C...

Страница 6: ...ng or cooling ON OFF 1 ON 2 3 3191S11 N1 T B1 T B2 T D3 Y1 3191S12 N1 T YE B1 T B2 T D3 Y1 Chilled heated ceiling 3 position heating or cooling 1 ON 2 3 Chilled ceiling and radiator ON OFF heating and cooling 1 ON 2 3 3191S11 N1 T B1 T B2 T D3 Y1 3191S13 N1 T B1 T D3 Y1 YR Y1 Heating or heating cooling valve actuator B1 Return air temperature sensor or external room temperature sensor optional YR ...

Страница 7: ... DIP switches diagram 1 stage compressor ON OFF heating or cooling 1 ON 2 3 1 stage compressor with electric heater heating or cooling ON OFF 1 ON 2 3 3181S31 N1 T B1 T D3 3181S32 N1 T YE B1 T D3 1 stage compressor ON OFF heating and cooling 1 ON 2 3 3181S35 N1 T B1 T D3 N1 Thermostat B1 Return air temperature sensor or external room temperature sensor optional YE Electric heater D3 Dewpiont senso...

Страница 8: ... min 60 mm diameters and min 40 mm depth 3 Control outputs KNX switching groups Ordering When ordering indicate both product number SSN number and name E g RDF600KN S55770 T293 room thermostat Order valve actuators separately Equipment combinations Type of unit Product no Data sheet Cable temperature sensor or changeover sensor QAH11 1 1840 Room temperature sensor QAA32 1747 Condensation monitor Q...

Страница 9: ... download For the maximal number of actuators in parallel refer to information in the data sheets of the selected actuators and to this list depending on which value is lower Parallel operation of max 6 SS actuators 3 pos is possible Parallel operation of max 10 on off actuators is possible Accessories Designation Product no SSN Data sheet Changeover mounting kit 50 pcs package ARG86 3 N3009 Plast...

Страница 10: ...parameters 4 Four buttons to control KNX actuators via KNX S mode functions switching dimming blinds control 8 bit scene Display 1 Operating mode Protection Comfort Economy Auto Timer according to schedule via KNX 2 Displays room temperature set points and control parameters Symbol indicates current room temperature 3 Fan mode Auto fan active Fan speed low medium high 4 Heating cooling mode Coolin...

Страница 11: ...he thermostat Warning No internal line protection for supply lines to external consumers Q1 Q2 Q3 Yxx Risk of fire and injury due to short circuits Adapt the line diameters as per local regulations to the rated value of the installed overcurrent protection device The AC 230 V mains supply line must have an external circuit breaker with a rated current of no more than 10 A Properly size the cables ...

Страница 12: ...er power is applied the thermostat resets and all LCD segments flash indicating that the reset was correct After the reset which takes about 3 seconds the thermostat is ready for commissioning by qualified HVAC staff If all DIP switches are OFF the display reads NONE to show that an application needs to be set via tool Each time the application is changed the thermostat reloads the factory setting...

Страница 13: ...NX network during commissioning Press buttons operating mode and simultaneously for 6 sec to activate programming mode which is indicated on the display with PrOg Programming mode remains active until thermostat identification is complete Assign device address P81 via HMI ACS or ETS With device address set to 255 the communication is deactivated no exchange of process data Use ETS to assign the KN...

Страница 14: ... Type Temperature range Cable length Digital input Operating action Contact sensing Parallel connection of several thermostats for one switch Insulation against mains voltage SELV QAH11 1 NTC 0 49 C Max 80 m Selectable NO NC SELV DC 0 5 V max 5 mA Max 20 thermostats per switch 4 kV reinforced insulation Function of inputs External temperature sensor heating cooling changeover sensor operating mode...

Страница 15: ...ironmental declaration CE1E3076_4en for RDF600KN RDF600KN S A5W00085841A RDF600KN VB contains data on environmentally compatible product design and assessments RoHS compliance materials composition packaging environmental benefit disposal General Connection terminals Minimal wiring cross section on L N Q1 Q2 Q3 Y11 Y21 Solid wires or prepared stranded wires 1 x 0 4 1 5 mm2 min 1 5 mm2 Housing fron...

Страница 16: ...C 230 V Q2 Control output Fan speed 2 AC 230 V Q3 Control output Fan speed 3 AC 230 V Y11 Y21 Control output Valve AC 230 V N O for normally closed valves output for compressor or output for electric heater X1 X2 Multifunctional input for temperature sensor e g QAH11 1 or potential free switch Factory setting X1 Operating mode switchover contact X2 External sensor function can be selected via para...

Страница 17: ...contact presence detector etc B1 B2 Temperature sensor return air temperature external room temperature changeover sensor etc CE KNX data CE KNX data 2 pipe 2 position 2 pipe 3 position Y11 Open Y21 Close 2 pipe and electric heater 4 pipe Y1 Heating Y2 Cooling 1 stage compressor C1 Heating and or C2 Cooling 1 stage compressor and electric heater L N 10A L N Y11 Y21 AC 230 V X1 M X2 N1 M1 Y1 5 2 A ...

Страница 18: ...21 Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www Siemens Switzerland Ltd 2019 Technical specifications and availability subject to change without notice www siemens com buildingtechnologies Dimensions Dimensions in mm 86 86 3076M01 30 16 3076M12 8 0 3076M13_01 ...

Отзывы: