Universal inputs
continued
Requirements for pulse inputs
Signal cables
Signal coupling
Type of contact
Mechanical signal source (Reed contact)
Max. pulse frequency
Min. pulse duration
Electronic signal source
Max. pulse frequency
Min. pulse duration
Insulating strength against mains potential
Recommendation: Shielded cables
Potential-free
Impulse contact
25 Hz
20 ms (incl. max. 10 ms bounce time)
100 Hz
5 ms
AC 3750 V as per EN 60950-1
Line length for:
Passive sensor signals LG-Ni 1000, T1, Pt 1000
Active signals DC 0…10 V
Status and impulse contacts
Max. 300 m
See data for signal-sending device
300 m
Relay outputs
Q1_,Q2_,Q3_,Q4_,Q7_,Q8_
Number
Relay with NC contact
Relay with NO contact
4 (terminals Q11,Q12 Q21,Q22,
Q31,Q32 Q41,Q42)
2 (terminals Q73,Q74 Q83,Q84)
External supply line fusing
NC contact, non-renewable fuse (slow)
NO contact, non-renewable fuse (slow)
Automatic line cutout
Release characteristic
Max. 3.15 A
Max. 5 A
Max. 13 A
B, C, D as per EN 60898
Line length
Max. 300 m
Relay contact data
Switching voltage
AC current (NC)
AC current (NO)
At 250 V
At 19 V
Switch-on current
Max. AC 250 V, min. AC 19 V
Max. 2 A ohm., 2 A ind. (cos
φ
= 0.6)
Max. 4 A ohm., 3 A ind. (cos
φ
= 0.6)
Min. 5 mA
Min. 20 mA
Max. 10 A (1 s)
Contact life at AC 250 V
At 0.1 A ohm.
At 0.5 A ohm.
At 2 A ohm.
At 4 A ohm.
Red. fact. at ind. (cos
φ
= 0.6)
Guide values:
2 x 10
7
switchings
(NC and NO)
2 x 10
6
switchings (NC)
4 x 10
6
switchings (NO)
3 x 10
5
switchings (NC)
6 x 10
5
switchings (NO)
3 x 10
5
switchings (NO only)
0.85 (NC and NO)
Insulating strength between:
Relay contacts and system electronics (reinforced insulation)
Neighboring relay contacts (operational insulation)
AC 3750 V, as per EN 60950-1
AC 1250 V, as per EN 60950-1
AC 230 V
Screw terminals for:
Solid / stranded wire (twisted or with ferrule)
1 solid / stranded wire per terminal
2 solid / stranded wires per terminal (max. 2)
Min. Ø 0.8 mm
0.5...2.5 mm
2
0.5...1.5 mm
2
Connecting terminals
Inputs and outputs
PC interface
Interface
Standard
Device class
Baud rate
USB V1.1 (universal serial bus)
RNDIS (remote network device
Interface specification)
Max. 12 Mbps (full speed)
Connecting cable for operator station
Cable length
Cable type for connection to PC/laptop
Cable type for connection to OZW775
Max. 5 m
USB type A
USB type B
Modem interface
Interface
Standard
Baud rate
RS-232, V.24 / EIA 232D
Max. 115 kbaud
Connecting cable for modem
Cable length
Cable type for connection to OZW775
Max. 15 m
D-sub 9-pin, plugs
14/18
Building Technologies
Central communication unit OZW775 V2.0
CE1N5663en
HVAC Products