background image

GAMMA

instabus

Technical Product Information

December 2014

IP Control Center N152

5WG1 152-1AB01

Siemens AG

N 152, 4 Pages

Technical Manual

Infrastructure & Cities Sector, Building Technologies
Control Products and Systems

ã

 Siemens AG 2014

Update: http://www.siemens.com/gamma

P. O. Box 10 09 53, D-93009 Regensburg

Subject to change wihout further notice

2.11.1.15/1

Product and function description

The IP Control Center N152 is a device for DIN-rail
mounting.

It offers the following functions:

·

  A web server for operating and observing KNX sys-

tems is incorporated in this device.

·

  A standard web browser displays the operating pages,

(tested browsers, see application program description)

·

  A graphics web editor projects a fully graphic view with

control and display elements in various styles.

·

 Application modules:

-

 

Time switch schedules with up to 300 time switch
commands per week

-

 

Scenes module with up to 5000 scenes or events

-

 

Full graphic Logic module with up to 1000 Logic
functions

-

 

Alarm function with up to 250 different alarm mes-
sages

-

 

Email function with up to 20 contacts

are configured via a graphics web editor.

·

  An additional smart editor allows the intuitive and

quick preparation of simple visualisations for smart-
phones with mobile browser or for room control units.

·

  It provides an interface to KNX installations via data

networks, using the Internet Protocol (IP). Concur-
rently, this device provides communication from KNX
devices with PCs or other data processing equipment
(KNXnet/IP tunnelling).

The device is configured with the settings using ETS 3/4.
It defines the data types for the 250 available KNX
communications objects and provides basic information
for the device and for network settings.

The following data types can be chosen at the parameter

setting of the communication objects:

·

 1 bit

·

  1 Byte (0…100%)

·

  1 Byte unsigned

·

 1 Byte signed

·

  2 Byte unsigned

·

 2 Byte signed

·

  2 Byte float

·

  4 Byte unsigned

·

 4 Byte signed

·

  4 Byte float

·

  14 Byte text

Further 1000 group addresses can be linked together di-

rectly with the visualisation components.

The following default settings can be placed on the de-
vice:

·

  The IP address of the device is assigned by ETS con-

figuration or automatically by a DHCP service in the IP
network. Assigning of the IP address by a DHCP ser-
vice allows changes to the IP address without config-
uring the device with the ETS.

·

  When configuring the device with a fixed IP address

and subnet mask, a standard gateway or router can
also be defined. This gives subscribers the opportunity
to access the Internet or another network.
If you have queries on setting the parameters IP ad-
dress of the device and subnet masks, as well as
DHCP, you should contact your local network adminis-
trator.

·

  You can set the port number of the integrated web

server.

·

  Web pages for viewing and the web editor can be pro-

tected separately with different passwords.

·

  The device can be set both as a time master (syn-

chronisation by time server via IP) and as a time slave
(synchronisation by KNX telegrams).

·

  A further parameter sets a read requirement. This will

send an update to the object values after a restart/bus
reset.

The device is delivered with a preset IP setting:

Delivery status:
IP address: 192.168.1.133

Additional Information

http://www.siemens.com/gamma

Содержание IP Control Center N152

Страница 1: ... with the settings using ETS 3 4 It defines the data types for the 250 available KNX communications objects and provides basic information for the device and for network settings The following data types can be chosen at the parameter setting of the communication objects 1 bit 1 Byte 0 100 1 Byte unsigned 1 Byte signed 2 Byte unsigned 2 Byte signed 2 Byte float 4 Byte unsigned 4 Byte signed 4 Byte...

Страница 2: ...64 V Constant current supply DC 24 V 1 3 A Rated output voltage DC 24 V Width 3 SU LOGO Power 24 V 2 5 A Rated input voltage AC 100 240 V wide range Input voltage range AC 85 264 V Constant current supply DC 24 V 2 5 A Rated output voltage DC 24 V Width 4 SU LOGO Power 24 V 4 A Rated input voltage AC 100 240 V wide range Input voltage range AC 85 264 V Constant current supply DC 24 V 4 A Rated out...

Страница 3: ...em DIN rail device can be installed in distribu tion boards surface or flush mounted or on any DIN rail complying with EN 60715 TH35 7 5 The connection to the bus line is established via the bus connector terminal red black on the top side The RJ45 socket on the device front side provides the connection to the Ethernet IP data network Mounting Snap the IP Control Center N152 Figure 2 B1 on to the ...

Страница 4: ...ing bus cables Figure 3 The bus connection block Figure 3 D2 can be used with single core conductors Ø 0 6 0 8 mm Remove approx 5 mm of insulation from the conduc tor Figure 3 D2 4 and plug it into the bus connection block Figure 3 D2 red black Disconnecting bus cables Figure 3 Unplug the bus connection block Figure 3 D2 and remove the bus cable conductor Figure 3 D2 4 while simultaneously wigglin...

Отзывы: