Note:

To ensure proper installation of the detector head
into the base, check that the wires are properly
dressed at installation.

a.Position all wires flat against the base.

b.Take up all slack in the outlet box.

c. Route wires away from connector terminals.

INSTALLATION OF DETECTOR HEAD

1. Align notch in detector cover to raised surface on

outer ring of base (See Figure 3).

2. Push detector head

into base and rotate
clockwise to make
electrical connections.
The detector auto-
matically stops and
locks into place.

3. To remove, push

detector head up into
the base while rotating
the detector head
counterclockwise. Continue to rotate counter-
clockwise

 

until stop is reached. Then pull

downward to disengage from base.

PROGRAMMING

Each detector on a loop must be programmed to
respond to a unique system address.

1.

To program the detector address, use the 

SIEMENS

Model FPI-32 Programmer/Tester. Refer to the

FPI-32 OPERATIONS MANUAL, 

P/N 315-090077.

2.

Record the loop and device number (system ad-
dress) for the detector on the detector label.

SENSITIVITY ADJUSTMENT

XL3 Systems

The sensitivity of each detector can be adjusted from
the System XL3 Control Panel. Refer to the 

SYSTEM

XL3 OPERATION, INSTALLATION, AND MAINTE-
NANCE MANUAL, 

P/N 315-083206.

MXL/MXL-IQ Control Panels

The sensitivity of each detector can be adjusted from
the MXL/MXL-IQ Control Panel. Refer to the 

MXL

OPERATION, INSTALLATION, AND MAINTENANCE
MANUAL, 

P/N 315-092036, or the 

MXL-IQ OPERATION,

INSTALLATION, AND MAINTENANCE MANUAL, 

P/N

315-093624, as applicable.

ICON-1 Modules (in IXL Systems)

The sensitivities of detectors on an ICON-1 module are
set from the IXL Control Panel. Refer to 

ICON-1

Instructions,

 P/N 315-093087, as well as the 

IXL

Programming Manual,

 P/N 315-092394, for additional

information.

TESTING AND SENSITIVITY MEASUREMENTS

XL3 Systems

Only qualified service personnel should test. Refer to
the 

SYSTEM XL3 OPERATION, INSTALLATION,

AND MAINTENANCE MANUAL, 

P/N 315-083206.

Test as frequently as required by the 

Installation and

Test Guidelines 

of NFPA 72. Obtain detector sensitivity

measurements from the System XL3 Control Panel.
Refer to the System XL3 Manual for further information.
The detector sensitivity indicated by the System XL3
Control Panel should fall within the range on the detector
nameplate label. If not, refer to 

DETECTOR CLEANING

on page 4.

MXL/MXL-IQ Control Panels

Only qualified service personnel should test. Refer to
the 

MXL OPERATION, INSTALLATION, AND

MAINTENANCE MANUAL, 

P/N 315-092036, or the

MXL-IQ OPERATION, INSTALLATION, AND MAIN-
TENANCE MANUAL,

 P/N 315-093624, as applicable.

Test as frequently as required by the 

Installation and

Test Guidelines of NFPA 72.

 Obtain detector sensitivity

measurements from the MXL/MXL-IQ Control Panel.
Refer to the MXL/MXL-IQ Manual for further
information. The detector sensitivity indicated by the
MXL/MXL-IQ Control Panel should fall within the range
on the detector nameplate label. If not, refer to

DETECTOR CLEANING 

 on page 4.

ICON-1 Modules (in IXL Systems)

Only qualified service personnel should test. Refer to
the IXL Manuals, P/Ns 315-092394 and 315-092371,
as well as the ICON-1 Instructions, P/N 315-093087,
for information. Test as required by the

 Installation and

Test Guidelines of NFPA 72.

 Obtain detector sensitivity

measurements from the IXL Control Panel. The
detector sensitivity indicated by the IXL Control Panel
should fall within the range on the detector nameplate
label. If not, refer to 

DETECTOR CLEANING

 on page 4.

Note:

To test for GO/NO GO operation, use 

SIEMENS

Test Gas, P/N 315-282747, and follow the
instructions on the label.

Figure 3

Detector Mounting

Содержание ILI-1

Страница 1: ...1AH Fire Safety Installation Instructions TO AVOID NUISANCE ALARMS WITH THESE DETECTORS DO NOT LOCATE the detectors next to an oil burner kitchen or garage where exhaust fumes can trigger an alarm Other causes of nuisance alarms are dust accumulation heavy concentrations of steam heavy pipe or cigar smoke aerosol sprays high air velocity or in an area of prolonged high relative humidity where cond...

Страница 2: ...actor that can only be provided by experienced qualified personnel DETECTOR WIRING Siemens Building Technologies Inc detectors should be interconnected as shown in Figure 1 and wired to the control panel by following the Wiring Diagram installed on the inside face of the control panel or in the Control Panel Manual provided Note any limitations on the number of detectors permitted on each circuit ...

Страница 3: ...rogramming Manual P N 315 092394 for additional information TESTING AND SENSITIVITY MEASUREMENTS XL3 Systems Only qualified service personnel should test Refer to the SYSTEM XL3 OPERATION INSTALLATION AND MAINTENANCE MANUAL P N 315 083206 Test as frequently as required by the Installation and Test Guidelines of NFPA72 Obtain detector sensitivity measurements from the System XL3 Control Panel Refer...

Страница 4: ...ribed below CLEANING PROCEDURE Clean by lightly brushing all open slots and by using the suction of a vacuum cleaner Because the suction may cause the detector to alarm it is recommended that power to the detector be disconnected during cleaning The detectors are not designed for thorough cleaning in the field When the detector sensitivity falls outside the acceptable limits for that detector the ...

Отзывы: