INTRODUCTION

The Model HZM from Siemens Industry, Inc. is an intelligent device that connects a
single zone of conventional devices to a DLC (FireFinder-XLS System) or FS-DLC (FS-
250 System) device loop. The HZM can power up to fifteen compatible 2-wire, ioniza-
tion or photoelectric smoke detectors or it can power one PB-1191 Beam Detector. It
can also monitor an unlimited number of shorting devices such as waterflow switches,
thermal detectors, manual stations, etc.

Each HZM can be assigned a custom message using either the Zeus Programming
Tool (FireFinder-XLS System) or the FS-CT2 (FS-250 System). Refer to the Zeus Quick
Start Manual, P/N 315-033875, or the FS-250 Programming Manual, P/N 315-049403,
as applicable. The alarm verification configuration is used 

only

 for non-shorting detectors.

The HZM supports Class A and Class B wiring. The module uses one address on the
device loop. It does not require any mechanical address programming. Use the DPU
Device Programming Unit to program and test the module.

HZM

HZM

FRONT

BACK

SIDE

ALARM

1

2

3

4

5

6

7

8

9

PROGRAMMING

POINTS

Figure 1

HZM Module

The HZM is not listed for use in mass notification applications.

Controls And Indicators

The HZM has a multicolor LED, visable through the cover plate, which indicates the
condition of the circuit. This multicolor LED displays red for alarm, yellow for trouble,
and green for normal operation (See Figure 1).

PRE-INSTALLATION

Setting The  Module Address

1.

Using the DPU Device Programming Unit, plug the programming cable into
the programming points on the HZM (See Figure 1).

2.

Set the address for the HZM by following the instructions in the DPU
Manual,

 

P/N 315-033260.

Remote Conventional Zone Module

Installation Instructions
Model HZM

Содержание HZM

Страница 1: ... Quick Start Manual P N 315 033875 or the FS 250 Programming Manual P N 315 049403 as applicable The alarm verification configuration is used only for non shorting detectors The HZM supports Class A and Class B wiring The module uses one address on the device loop It does not require any mechanical address programming Use the DPU Device Programming Unit to program and test the module HZM HZM FRONT...

Страница 2: ...ows the Class B wiring 1 2 3 4 5 6 7 8 9 EARTH DEVICE LOOP 24VDC POWER LINE 2 LINE 1 STYLE D CLASS A DCLA EOL EOL DEVICE IS 4 7K 1 4W P N 140 820188 FOR CANADIAN APPLICATIONS USE MODEL EL 33 WITH 4 7K 1 4W RESISTOR Figure 2 HZM Initiating Devices Wiring Diagram Class A Style D ULC DCLA Installation Figure 3 HZM Initiating Devices Wiring Diagram Class B Style B ULC DCLB Installation DEVICE LOOP 24V...

Страница 3: ... jumper J1 c Remove the 2 position plug from J1 d Reassemble the circuit board and plastic cover using the screw that was removed in the first step e Be sure to use the correct end of line device with the HZM in this configuration PB 1191 A B C D E F 1 2 3 4 5 6 7 8 9 BEAM DETECTOR WIRING CLASS B STYLE B ULC DCLB HZM J1 EARTH 3 6K 1 4W EOL RESISTOR P N 140 820185 DO NOT CONNECT MORE THAN ONE PB 11...

Страница 4: ... 5 5 6 6 6 6 7 7 7 7 8 8 8 8 9 9 9 9 HZM HZM HZM HZM LINE 2 LINE 1 1 1 1 1 2 2 2 2 3 3 3 3 4 4 4 4 5 5 5 5 6 6 6 6 7 7 7 7 8 8 8 8 9 9 9 9 HZM HZM HZM HZM LINE 2 LINE 1 NOT USED NOT USED NOT USED 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 9 9 9 HZM HZM HZM LINE 2 RETURN LINE 2 OUT LINE 1 OUT LINE 1 RETURN 1 1 1 2 2 2 3 3 3 4 4 4 5 5 5 6 6 6 7 7 7 8 8 8 9 9 9 HZM HZM HZM LINE 2 RETURN LINE 2 O...

Страница 5: ...power connection Refer to Figure 7 for the wiring diagram 1 1 1 1 1 2 2 2 2 2 3 3 3 3 3 4 4 4 4 4 5 5 5 5 5 6 6 6 6 6 7 7 7 7 7 8 8 8 8 8 9 9 9 9 9 HZM HZM HZM HZM HZM CLASS B INSTALLATION T TAPPING ALLOWED TO 24 VDC SEE NOTE 5 Figure 7 HZM 24 VDC Wiring Diagram Mounting 1 Mount the HZM in a standard two gang electrical box The box must have a depth of at least 3 inches 2 When the field wiring for...

Страница 6: ... a t o t s m h o 5 3 e g n a R e g a t l o V y r o s i v r e p u S e v a w l l u f d e r e t l i f C D V 5 4 2 8 1 t n e r r u C e n o Z x a M A m 4 3 r e w o P C D V 4 2 e g n a R e g a t l o V C D V 2 8 2 8 8 1 t n e r r u C x a M A m 0 0 1 t n e r r u C y b d n a t S A m 6 6 p o o L C L D S F C L D t n e r r u C x a M A m 1 ELECTRICAL RATINGS ...

Страница 7: ...needs Such a security concept may result in additional site specific preventive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...

Страница 8: ...y Inc Building Technologies Division Florham Park NJ Siemens Canada Ltd 1577 North Service Road East Oakville Ontario L6H 0H6 Canada P N 315 034850 8 This page has been left intentionally blank Document ID A6V10233195 ...

Отзывы: