Operating
7.5 Discrete inputs
HydroRanger 200 HMI
106
Operating Instructions, 06/2018, A5E36281317-AC
7.4.1
Backup level override parameters
Discrete Input Number (2.9.1.2.)
Sets the discrete input as the source of a level reading override
Level Override Value (2.9.1.3.)
Substitutes value for current reading when Discrete Input Number (2.9.1.2.) (Page 208) is
activated. Value is added in current units and is valid only for the following:
●
Level
●
Space
●
Distance
●
Difference
●
Average modes of operation
●
Head level in OCM mode
Example
A high level backup switch is connected to Digital Input 2 in the same application as
Transducer 1 at level value 4.3 m.
Settings
Parameter
Index
Value
Discrete Input Number (2.9.1.2.) (Page 208)
1
DI 2 Override Signal (Page 208)
Discrete Input Number (2.9.1.2.) (Page 208)
2
*No Override (Page 208)
Level Override Value (2.9.1.3.) (Page 208)
1
4.3
Level Override Value (2.9.1.3.) (Page 208)
2
–
When the level rises to 4.3 m and the switch is activated, the reading is forced to 4.3 m
where it stays until the switch is de-activated.
Override Time Delay (2.9.1.4.)
Sets the time (in seconds) used to calm the override condition input
7.5
Discrete inputs
Discrete input logic affects the reaction of the discrete input. Normal state is the standard
operation, with the device sensing the material level and controlling the pumps.
Содержание HydroRanger 200 HMI
Страница 2: ......
Страница 20: ...Introduction 1 5 Notes on warranty HydroRanger 200 HMI 18 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 24: ...Safety notes HydroRanger 200 HMI 22 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 28: ...Description 3 5 Modbus communication HydroRanger 200 HMI 26 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 159: ...Parameter reference 8 2 Parameter indexing HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 157 ...
Страница 276: ...Parameter reference 8 10 Language 6 HydroRanger 200 HMI 274 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 322: ...Pump control reference B 13 Other pump controls HydroRanger 200 HMI 320 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 352: ...Communications C 41 Single parameter access SPA HydroRanger 200 HMI 350 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 354: ...Updating software HydroRanger 200 HMI 352 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 359: ...HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 357 Conduit entry for Class I Div 2 applications F ...
Страница 360: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI 358 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 361: ...Conduit entry for Class I Div 2 applications HydroRanger 200 HMI Operating Instructions 06 2018 A5E36281317 AC 359 ...
Страница 362: ......
Страница 372: ...Programming chart G 1 Programming chart HydroRanger 200 HMI 370 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 390: ...LCD menu structure H 1 LCD Menu Structure HydroRanger 200 HMI 388 Operating Instructions 06 2018 A5E36281317 AC ...
Страница 403: ......