background image

Siemens Building Technologies, Inc

.                                                                                                                                                         P84391-003B 

8 Fernwood Road                                                                                                                                                                                             Sheet 1 of 4 

 Florham Park, New Jersey 07932 
 
 

 

 

 

INSTALLATION INSTRUCTIONS 

MULTI-CANDELA FOUR WIRE HORN STROBE APPLIANCES 

(WALL MOUNT VERSION) 

 

IMPORTANT – 

All audible and visual signaling appliances must be 

installed in accordance with all applicable national and local fire alarm 
codes and any other required regulatory agencies. 

 

Series HS-MC Multi-Candela Horn Strobe provides four selectable 
candela settings (15, 30, 75, 110).  The HS-MC allows for independent 
operation of the strobe circuit and the horn circuit.  It is the ideal choice 
for retrofit applications as well as new installations.  The HS-MC 
appliance is UL Listed under Standard 1971 for Signaling Appliances 
for the Hearing Impaired and UL Standard 464 for Audible Signal 
Appliances. The HS-MC is also ULC Listed under Standard CAN/ULC-
S526-02 for Visual Signaling Appliances and Standard CAN/ULC-
S525-99 for Audible Signaling Appliances for Fire Alarm Systems.  It is 
listed for 

indoor use only

 and can be mounted to double-gang, 4” 

backbox, 100mm European backbox or MT-SUR-BOX surface 
backbox (See wiring and mounting information).  This appliance is 
listed for 

wall mounting only

.  The HS-MC appliance uses a xenon 

flashtube with solid state circuitry enclosed in a polycarbonate lens to 
provide maximum visibility and reliability for effective visible signaling. 
 
Siemens Series HS appliances provide a selectable continuous or 
Code 3 horn tone and non-synchronized strobe when connected 
directly to a Fire Alarm Control Panel (FACP).  They can also provide a 
synchronized Code 3 (or March Time) horn tone and synchronized 
strobe when connected to a notification appliance circuit running the 
Siemens sync protocol.  HS appliances  can be field set for High (HI), 
medium (MED) dBA or low (LO) dBA sound output.  .   

 
NOTE:

  The Code 3 temporal pattern (1/2 second on, 1/2 second off, 

1/2 second on, 1/2 second off, 1/2 second on, 1-1/2 off and repeat) is 
specified by ANSI and NFPA 72 for standard emergency evacuation 
signaling.  

The Code 3 Horn should be used only for fire 

evacuation signaling and not for any other purpose. 

 
The HS-MC is designed for use with either filtered DC or unfiltered full-
wave-rectified (FWR) input voltage.  All inputs are polarized for 
compatibility with standard reverse polarity supervision of circuit wiring 
by an FACP. 

 
NOTE:  

All Canadian Installations should be in accordance with the 

Canadian Standard for the Installation of Fire Alarm Systems – 
CAN/ULC-S524-01 and Canadian Electrical Code, Part 1.  Final 
acceptance is subject to authorities having jurisdiction (AHJ). 
 
NFPA 72/ANSI 117.1 conform to ADAAG Equivalent Facilitation 
Guidelines in using fewer, higher intensity strobes within the same 
protected area. 
 

NOTE:  

Refer to P/N 315-096363 for the maximum number of 

appliances on a single notification appliance circuit. 

 

 

 

 
 
SPECIFICATIONS: 
 

Table 1: UL/ULC Listed Models and Ratings

 

 

Model* 

Operating Voltage (Special Application) 

 Per UL 1971 
(VDC/VRMS) 

Voltage Range Per 
CAN/ULC-S526-02 

(VDC/VRMS) 

Strobe  

Candela 

(cd) 

HS-MC 16.0-33.0 

20.0-31.0 

15/30/75/110 

*Available in red and white. 

 

 

Table 2:  dBA Sound Output for 24VDC Models 

Reverberant Per UL 464 

Anechoic dBA @ 10 Ft. Per CAN/ULC-S525-99 

 

Description 

 

Volume 

16.0VDC 24VDC 

33.0VDC 

20.0VDC  24VDC  31.0VDC 

 Low 

80  83 86 88  90 

91 

Continuous Horn 

Medium 

85 

88 

91 

93 

95 

97 

 High  88  91 93 97  99  100 
 Low 

75  79 82 88  90 

91 

Code 3 Horn or  

Medium 

80 

84 

86 

93 

95 

97 

March Time** 

High 

84 

87 

89 

97 

99 

100 

**Available in sync mode only. 

 

Содержание HS-MC Series

Страница 1: ...strobe when connected to a notification appliance circuit running the Siemens sync protocol HS appliances can be field set for High HI medium MED dBA or low LO dBA sound output NOTE The Code 3 temporal pattern 1 2 second on 1 2 second off 1 2 second on 1 2 second off 1 2 second on 1 1 2 off and repeat is specified by ANSI and NFPA 72 for standard emergency evacuation signaling The Code 3 Horn shou...

Страница 2: ...m RMS Current Amps Input Voltage Lo Med Hi DC 16 33VDC 0 027 0 068 0 110 FWR 16 33VRMS 0 041 0 050 0 094 Table 3A Current Ratings Strobe Only Maximum RMS Current Amps Input Voltage 15cd 30cd 75cd 110cd DC 16 33VDC 0 064 0 098 0 175 0 233 FWR 16 33VRMS 0 108 0 164 0 268 0 368 THESE APPLIANCES WERE TESTED TO THE VOLTAGE LIMITS OF 16 0 33 0 VOLTS FOR 24V MODELS USING FILTERED DC OR UNFILTERED FULL WA...

Страница 3: ... HS MC audible is connected to a coded system the continuous horn setting must be used WIRING AND MOUNTING INFORMATION Figure 4 Audible signal and strobe operate independently Figure 4A Audible and strobe operate in unison Shunt wires are supplied STR AUD TB1 FROM FACP OR PRECEDINGAPPLIANCE TO NEXTAPPLIANCE OR EOLR FROM FIRE ALARM CONTROL PANEL FACP OR PRECEDINGAPPLIANCE TO NEXTAPPLIANCE OR END OF...

Страница 4: ...C to the backbox verifying that it is seated and aligned correctly 7 Fasten the HS MC to the backbox using the supplied screws The HS MC 110cd setting is Listed for use in sleeping or non sleeping areas when installed in accordance with appropriate NFPA Standards and the AHJ WARNING A SMALL POSSIBILITY EXISTS THAT THE USE OF MULTIPLE STROBES WITHIN A PERSON S FIELD OF VIEW UNDER CERTAIN CIRCUMSTAN...

Отзывы: