Siemens Building Technologies, Inc.
8 Fernwood Road
Florham Park, New Jersey 07932
Siemens Building Technologies, Ltd.
2 Kenview Boulevard
Brampton, Ontario L6T 5E4
P/N 315-033170-2
Страница 1: ...ure 1 for the location of the two input terminals and two output terminals Line 1 and Line 2 can be either line of the loop The HLIM may be used in two circuit configurations as follows Class B See Figure 2 In Class B wiring each HLIM isolates a branch on the circuit Note that a short on the main branch causes the entire loop to fail To prevent this mount the HLIMs at the FireFinder XLS enclosure ...
Страница 2: ... between HLIMs cannot exceed 20 ohms 5 Do not install more than 15 HLIMs per DLC loop 6 All circuits are supervised 7 Refer to DLC Installation Instructions P N 315 033090 for the list of compatible devices 8 All terminals are power limited 1 All wiring must comply with national and local codes 2 In order to provide adequate protection it is recom mended that you do not install more than 20 device...
Страница 3: ...ctrical box that is 2 1 8 inches deep Connect the field wiring Press the HLIM into the box and fasten the module plate to the box Cover the module front plate with the plate supplied and fasten with screws supplied ELECTRICAL RATINGS Input power 24 VDC 1mA max SWITCHPLATE 4 INCHES SQUARE SUPPLIED SWITCHPLATE SUPPLIED 4 INCHES SQUARE 4 INCH SQUARE BOX 2 1 8 INCHES DEEP DOUBLE GANG BOX 3 1 2 INCHES ...