Siemens Building Technologies

Fire Safety

P/N 315-033170-2

OPERATION

The 

SIEMENS 

Model HLIM Loop Isolator Module isolates short circuits on FireFinder-

XLS analog loops. By placing devices between HLIMs during installation, a short in
the wiring within that group is disconnected from the rest of the loop. The remainder

Figure 1

The HLIM-1 Loop Isolator Module

does not have a loop address and therefore does not require address programming
nor does it reduce the loop capacity below 252 devices.

Remove all system power before installation, first the battery and then the AC.

INSTALLATION

The HLIM is a polarity insensitive module. Refer to Figure 1 for the location of the
two input terminals and two output terminals. Line 1 and Line 2 can be either line of
the loop.

The HLIM may be used in two circuit configurations as follows:

Class B

(See Figure 2) In Class B wiring each HLIM isolates a branch on the circuit. Note that
a short on the main branch causes the entire loop to fail. To prevent this, mount the
HLIMs at the FireFinder-XLS enclosure and run each branch independently.

of the devices continue
to operate. The HLIM
operates in both Class A
and Class B circuits.

A yellow LED flashes
when a device detects a
short circuit. The HLIM
then isolates that part of
the loop. When the short
is removed, the HLIM
automatically restores
the loop to normal
operation. The HLIM

FRONT

BACK

FAULT

IN - LINE 1
IN - LINE 2
OUT - LINE 1
OUT - LINE 2

Loop Isolator Module

Installation Instructions
Model HLIM

Содержание HLIM

Страница 1: ...ure 1 for the location of the two input terminals and two output terminals Line 1 and Line 2 can be either line of the loop The HLIM may be used in two circuit configurations as follows Class B See Figure 2 In Class B wiring each HLIM isolates a branch on the circuit Note that a short on the main branch causes the entire loop to fail To prevent this mount the HLIMs at the FireFinder XLS enclosure ...

Страница 2: ... between HLIMs cannot exceed 20 ohms 5 Do not install more than 15 HLIMs per DLC loop 6 All circuits are supervised 7 Refer to DLC Installation Instructions P N 315 033090 for the list of compatible devices 8 All terminals are power limited 1 All wiring must comply with national and local codes 2 In order to provide adequate protection it is recom mended that you do not install more than 20 device...

Страница 3: ...ctrical box that is 2 1 8 inches deep Connect the field wiring Press the HLIM into the box and fasten the module plate to the box Cover the module front plate with the plate supplied and fasten with screws supplied ELECTRICAL RATINGS Input power 24 VDC 1mA max SWITCHPLATE 4 INCHES SQUARE SUPPLIED SWITCHPLATE SUPPLIED 4 INCHES SQUARE 4 INCH SQUARE BOX 2 1 8 INCHES DEEP DOUBLE GANG BOX 3 1 2 INCHES ...

Страница 4: ...Siemens Building Technologies Inc 8 Fernwood Road Florham Park New Jersey 07932 Siemens Building Technologies Ltd 2 Kenview Boulevard Brampton Ontario L6T 5E4 P N 315 033170 2 ...

Отзывы: