inst_h3.fm
P31003-H3560-S403-54-7620, 09/05
HiPath 3000 V6.0, HiPath 5000 V6.0, Provisional Service Manual
4-169
Installing HiPath 3000
Installing HiPath 3550, HiPath 3350, HiPath 3500, and HiPath 3300
You will find information on the design and dimensions in the following section:
●
HiPath 3550 Section 2.2.2.3
●
HiPath 3350 Section 2.2.2.4
4.4.3.1.1
For U.S. only: AC outlet
The AC connection must fulfill the requirements specified in Table 4-20.
AC Power Outlet Requirements
●
The power source may not be more than 2 m (6 ft.) from the system.
●
The power source must supply a voltage of 120 V AC (single phase, fused) in 50-60 Hz.
●
A warning should be attached to the circuit breaker to prevent accidental removal of power.
●
An independent electric circuit with an isolated ground conductor should be used.
●
Recommendation: Add a power surge protector between the outlet and the system.
Table 4-20
Electrical Connection Values (for U.S. only)
Nominal
voltage
Nominal voltage range
Nominal Frequency
Range
Wall Outlet Configura-
tions
from to from to
120 V AC/
60 Hz
110 V AC
130 V AC
47 Hz
63 Hz
NEMA 5-15, 2-pin, 3-
wire, earth
Содержание HiPath 3000 V3.0 or later Gigaset M1 Professional