Siemens HI320C Скачать руководство пользователя страница 3

Fire Safety & Security Products

Building Technologies

10.2005

I

1

General

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

1.1

Characteristics

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

1.2

Construction

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

2

Technical data

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

3

Design

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

4

Response characteristics

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

5

Application

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

5.1

Compatibility

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

5.2

Adjustment functions

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

5.3

Application

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

5.4

Installation

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

6

Commissioning

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

7

Maintenance

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

7.1

Functional check / overhaul

. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 

Содержание HI320C

Страница 1: ...Building Technologies Fire Safety Security Products Synovat Fire detection system HI320C HI322C Heat detectors Description ...

Страница 2: ... in full or in part nor to make them available to any third party without our prior express written authorization nor to use it for any purpose other than for which it was delivered to him Nous nous réservons tous les droits sur ce document ainsi que sur l objet y figurant La partie recevant ce document reconnaît ces droits et elle s engage à ne pas le rendre accessible à des tiers même partiellem...

Страница 3: ...al 1 1 1 Characteristics 1 1 2 Construction 2 2 Technical data 3 3 Design 4 4 Response characteristics 5 5 Application 5 5 1 Compatibility 5 5 2 Adjustment functions 5 5 3 Application 5 5 4 Installation 6 6 Commissioning 6 7 Maintenance 6 7 1 Functional check overhaul 6 ...

Страница 4: ...Fire Safety Security Products Building Technologies II 10 2005 ...

Страница 5: ...tor class A2 with rate of rise and maximum temperature activation for areas with higher temperature fluctuation Response behaviour immune to deceptive phenomena with rapid and slow increase in temperature through Intelligently designed differential characteristics Precise maximum temperature alarm activation with quality thermosensor High degree of reliability and long term stability High resistan...

Страница 6: ...LED provides an on site alarm signal Two additional external response indicators can be connected to the base The detectors are fully electronic and are not subject to wear and tear The protective cover can be easily removed for cleaning should the case arise The SO320 detector base is mounted on the ceiling or onto the base attachment SOA322 in case of surface mounted wiring and connected to the ...

Страница 7: ...time tR s 1 UR 1V Response sensitivity HI320C EN 54 5 class A1R temperature increase Release temperature static dT Ta C C 20 54 40 62 dT dt 10K min dT dt 0 2K min HI322C EN 54 5 class A2 Release temperature static Release temperature dynamic dT Ta C C 54 70 70 dT dt 0 2K min dT dt 10K min Remote response indicator output current DC mA 10 in alarm condition total current one or two indicators conne...

Страница 8: ...attached to a holder The measuring resistor Rm is located in the tip of the protection cover and measures the ambient temperature The housing temperature is measured with resistor Rg The open protection housing means that the ambient temperature has an almost un hindered effect on the sensor and protects it against mechanical damage NTC Temperature sensors Fig 1 Detector design ...

Страница 9: ... C rate of rise and maximum 5 Application 5 1 Compatibility Detection lines SynoLINE300 Base SO320 5 2 Adjustment functions None 5 3 Application The HI320C HI322C can be used up to a temperature of 50 C and are especially suitable for monitoring rooms and installations in which in the event of fire a rapid increase in temperature is to be expected or where other types of detector cannot be used be...

Страница 10: ...ectors unnecessarily only insert them in the bases immediately prior to commissioning Activate detectors with detector tester RE6T If the response indicator at the detector lights up the detector is operating correctly The line test set DZ1195 can be used for the final testing of installed detection lines 7 Maintenance 7 1 Functional check overhaul A functional check of the detectors must be perfo...

Страница 11: ...Fire Safety Security Products Building Technologies Back 7 10 2005 ...

Страница 12: ...0 2005 Document no Edition 1703_d_en_ 10 2005 International Headquarters Gubelstrasse 22 Fire Safety Security Products CH 6301 Zug Manual Section DS11 1 2 Siemens Schweiz AG Building Technologies Group Tel Fax www sbt siemens com 41 41 724 24 24 41 41 724 35 22 ...

Отзывы: