3
•
Take up all slack in the outlet box.
•
Route wires away from connector terminals.
To Install Detector Head:
•
Align LED in detector with LED symbol on base and
insert detector into base.
•
Rotate detector counterclockwise while gently press-
ing on it until the detector seats fully into base.
•
Then rotate the detector clockwise until it stops and locks
in place. Insert optional locking screw (Order Model LK-11).
To Remove Detector Head:
•
Loosen locking screw, if installed. Then rotate the
detector counter clockwise until stop is reached.
•
Pull detector out of base.
DETECTOR TESTING
Only qualified service personnel should test. To assure proper
operation of the detector and control panel, both the Sensitivity
and Functional Test should be conducted. The minimum test
schedule may be found in the current edition of NFPA 72 for
installations in the U.S., and CAN/ULC-S537, The Verification of
Fire Alarm Systems, for installations in Canada.
The HFP-11/HFPT-11 detectors can be tested individually us-
ing the DPU. Refer to the DPU Manual, P/N 315-033260.
Sensitivity Measurement (FireFinder-XLS)
Refer to the FireFinder-XLS Manual, P/N 315-033744, for in-
structions on applying the
Sensitivities
mode.
STEP 1
Press the
Menu
button on the PMI/PMI-2
(upper right) and select the
Report
option by
pressing the button with the lit green triangle
pointing to the Report Tab.
STEP 2
Press the
More Info
button on the PMI/PMI-2
to navigate to the desired loop or specific device
as follows:
•
Press the
More Info
button once to display a list
of FireFinder-XLS nodes; use the up and down
buttons to select the desired node.
•
Press the
More Info
button again to display a list
of FireFinder-XLS modules; use the up and down
buttons to select the desired module.
•
Press the
More Info
button again to display a list
of FireFinder-XLS devices; use the up and down
buttons to select the desired device.
STEP 3
Once at the desired module/loop or device,
select the
Status
option by pressing the button
with the lit green triangle pointing to the Status
Tab. The screen displays several options which
can be selected using the Touch Screen.
STEP 4
“Touch” the box labelled
Sensitivities
. This will
highlight the box (reverse video) to indicate that
it has been selected.
STEP 5
Select the
Execute
option by pressing the button
with the lit green triangle pointing to the Execute
Tab. The system reads all device sensitivities for
the module/loop or device and displays it on the
PMI/PMI-2 screen. This sensitivity report can
then be printed by selecting the
option.
Functional Test
Perform a functional (Go, No-Go) test by activating the detec-
tor using
Test Gas, TG-11, P/N 500-649750, following the in-
struction on the label. This test is simply used to ensure that
smoke can enter the sensing chamber and alarm the control
panel when the detector reaches the programmed obscura-
tion (concentration) level.
For FireFinder-XLS, refer to the FireFinder-XLS Manual, P/N
315-033744, for additional information. Follow the steps be-
low to disable ASD for testing:
STEP 1
Press the
Menu
button on the PMI/PMI-2
(upper right) and select the
Maintenance
(Maint)
option by pressing the button with the
lit green triangle pointing to the Maint Tab.
STEP 2
Press the
More Info
button on the PMI/PMI-2
to navigate to the desired loop or specific device
as follows:
•
Press the
More Info
button once to display a list
of FireFinder-XLS nodes; use the up and down
buttons to select the desired node.
•
Press the
More Info
button again to display a list
of FireFinder-XLS modules; use the up and down
buttons to select the desired module.
•
Press the
More Info
button again to display a
list of FireFinder-XLS devices; use the up and
down buttons to select the desired device.
TO INITIATING
CIRCUIT OF
SIEMENS
INDUSTRY, INC.
COMPATIBLE
CONTROL UNIT
OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
RL-HW / RL-HC
TO NEXT BASE
TO NEXT BASE
DO NOT
USE AN
END OF
LINE
DEVICE
DETECTOR BASE
MODEL DB-11
LINE 1**
LINE 2**
5
6
1a
TB1
TB3
TB2
1b
5
6
1a
1b
RELAY*
CONTACTS
3A, 120 VAC
3A, 30 VDC
REMOTE RELAY
BASE MODEL DB-HR
*The relay contacts are shown after System reset, which represents the non-alarm condition.
**HFP-11/HFPT-11 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.
5+
NO
C
NC
6–
5+
NO
C
NC
6–
DO NOT
USE AN
END OF
LINE
DEVICE
Figure 2
Installation and Wiring Diagram