Take up all slack in the outlet box.

Route wires away from connector terminals.

To Install Detector Head:

Align LED in detector with LED symbol on base and
insert detector into base.

Rotate detector counterclockwise while gently press-
ing on it until the detector seats fully into base.

Then rotate the detector clockwise until it stops and locks
in place. Insert optional locking screw (Order Model LK-11).

To Remove Detector Head:

Loosen locking screw, if installed. Then rotate the
detector counter clockwise until stop is reached.

Pull detector out of base.

DETECTOR TESTING

Only qualified service personnel should test. To assure proper
operation of the detector and control panel, both the Sensitivity
and Functional Test should be conducted. The minimum test
schedule may be found in the current edition of NFPA 72 for
installations in the U.S., and CAN/ULC-S537, The Verification of
Fire Alarm Systems, for installations in Canada.

The HFP-11/HFPT-11 detectors can be tested individually us-
ing the DPU. Refer to the DPU Manual, P/N 315-033260.

Sensitivity Measurement (FireFinder-XLS)

Refer to the FireFinder-XLS Manual, P/N 315-033744, for in-
structions on applying the 

Sensitivities

 mode.

STEP 1

Press the

 Menu

 button on the PMI/PMI-2

(upper right) and select the

 Report 

option by

pressing the button with the lit green triangle
pointing to the Report Tab.

STEP 2

Press the 

More Info

 button on the PMI/PMI-2

to navigate to the desired loop or specific device
as follows:

Press the 

More Info

 button once to display a list

of FireFinder-XLS nodes; use the up and down
buttons to select the desired node.

Press the 

More Info

 button again to display a list

of FireFinder-XLS modules; use the up and down
buttons to select the desired module.

Press the 

More Info

 button again to display a list

of FireFinder-XLS devices; use the up and down
buttons to select the desired device.

STEP 3

Once at the desired module/loop or device,
select the 

Status 

option by pressing the button

with the lit green triangle pointing to the Status
Tab. The screen displays several options which
can be selected using the Touch Screen.

STEP 4

“Touch” the box labelled 

Sensitivities

. This  will

highlight the box (reverse video) to indicate that
it has been selected.

STEP 5

Select the 

Execute

 option by pressing the button

with the lit green triangle pointing to the Execute
Tab. The system reads all device sensitivities for
the module/loop or device and displays it on the
PMI/PMI-2 screen. This sensitivity report can
then be printed by selecting the 

Print

 option.

Functional Test
Perform a functional (Go, No-Go) test by activating the detec-
tor using

 

Test Gas, TG-11, P/N 500-649750, following the in-

struction on the label. This test is simply used to ensure that
smoke can enter the sensing chamber and alarm the control
panel when the detector reaches the programmed obscura-
tion (concentration) level.

For FireFinder-XLS, refer to the FireFinder-XLS Manual,  P/N
315-033744, for additional information. Follow the steps be-
low to disable ASD for testing:

STEP 1

Press the

 Menu

 button on the PMI/PMI-2

(upper right) and select the

 Maintenance

(Maint) 

option by pressing the button with the

lit green triangle pointing to the Maint Tab.

STEP 2

Press the 

More Info

 button on the PMI/PMI-2

to navigate to the desired loop or specific device
as follows:

Press the 

More Info

 button once to display a list

of FireFinder-XLS nodes; use the up and down
buttons to select the desired node.

Press the 

More Info

 button again to display a list

of FireFinder-XLS modules; use the up and down
buttons to select the desired module.

Press the 

More Info

 button again to display a

list of FireFinder-XLS devices; use the up and
down buttons to select the desired device.

TO INITIATING
CIRCUIT OF
SIEMENS
INDUSTRY, INC.
COMPATIBLE
CONTROL UNIT

OPTIONAL
REMOTE
ALARM
INDICATOR
MODELS
RL-HW / RL-HC

TO NEXT BASE

TO NEXT BASE

DO NOT
USE AN
END OF
LINE
DEVICE

DETECTOR BASE
MODEL DB-11

LINE 1**

LINE 2**

5

6

1a

TB1

TB3

TB2

1b

5

6

1a

1b

RELAY*
CONTACTS
3A, 120 VAC
3A, 30 VDC

REMOTE RELAY
BASE MODEL DB-HR

*The relay contacts are shown after System reset, which represents the non-alarm condition.

**HFP-11/HFPT-11 is a polarity insensitive detector. Line 1 and Line 2 can be either line of the loop.

5+

NO

C

NC

6–

5+

NO

C

NC

6–

DO NOT
USE AN
END OF
LINE
DEVICE

Figure 2
Installation and Wiring Diagram

Содержание HFPT-11

Страница 1: ...tion Because the amplitude and duration of deceptive phenomena are un bounded the rule of thumb is to keep detectors as far as practi cal from sources that can produce an unusually large quantity of smoke forabout a minute This effort during placement of detec torswithinaFirePrintApplicationenhancestheabilityofFirePrint s deceptive phenomena rejection Avoid close proximity of detec tors to smoke s...

Страница 2: ...r the FS 250 Manual P N 315 049353 OPERATION LED Indicators The Model HFP 11 HFPT 11 contains an LED indicator ca pable of flashing either one of three distinct colors green yellow or red During each flash interval the microprocessor based detector checks the following For smoke in its sensing chamber That its smoke sensitivity is within the range indicated on the nameplate label h s a l F r o l o...

Страница 3: ...which can be selected using the Touch Screen STEP 4 Touch the box labelled Sensitivities This will highlight the box reverse video to indicate that it has been selected STEP 5 Select the Execute option by pressing the button with the lit green triangle pointing to the Execute Tab The system reads all device sensitivities for the module loop or device and displays it on the PMI PMI 2 screen This se...

Страница 4: ...Notify facility personnel that the system is being serviced so that any alarm soundings can be ignored during the pe riod of service CLEANING PROCEDURE See Figure 3 1 Notify the proper personnel that the fire alarm system is being serviced P N 315 033290 11 Siemens Industry Inc BuildingTechnologies Division Florham Park NJ Siemens Canada Limited 2 Kenview Boulevard Brampton Ontario L6T 5E4 Canada ...

Отзывы: