DISPLAY MODULE AND OFFICE CONFIGURATION EDITOR
_________________________________________________________________________________________________________
3-114
SIG-00-22-02 JUNE 2022 (Revised September 2022)
Version: B.1
Figure 3-166 Display Programming Log Verbosity Settings
3.5.2.11.5
Security
The security page allows the user to enable or disable the Maintainer password protection using
the
Security Enabled
field. This defaults to
None
. When the
Security Enabled
is set to
Maintainer the Maintainer Password field appears and the user can type in the required
password.
On returning to this screen, the password cannot be edited unless the correct password is
entered. See Section 3.1.2.6 for details.
If security has been enabled, the user will need to enter this password on the local user
interface to be able to edit GCP MCF parameters. Also, the user will need to log into the Web UI
with this password to be able to edit GCP MCF parameters. The user can still log into the Web
UI using the default GCP5000 password, but the configuration will be read-only.
Session Inactivity Timeout: 5 to 60 mins, the default is 20min. This is used to timeout the WebUI
if there is no activity on the GCP for the configured time.
NOTE
Be sure to have the password handy, in the event the Security
function is enabled.