Intended use

The FT2008/FT2009 LED annunciator enables the fire
detection system to be displayed and operated in a
simplified way. The FT2008 provides 2×16 LEDs to
display alarm/trouble events. The FT2009 provides 2×32
LEDs to display alarm/trouble events. Both devices are
operated on the UFP line.

This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
(1) This device may not cause harmful interference.
(2) This device must accept any interference received,
including interference that may cause undesired operation.

Package contents

The following are included in the scope of delivery:

l

FT2008-U1/FT2008-R1 or FT2009-U1/FT2009-R1

l

Cable ties (2 pcs)

l

EOL jumper connecter (1 pcs)

Safety instructions

Risk of injury to persons and damage to property

Please observe the following safety instructions:

l

The devices are only intended for stationary installation
in dry rooms.

l

The devices may only be connected to the UFP line.

l

If panel AUX power is not used, an UL listed/recognized
for fire use, regulated, power limited 24V DC power
supply is required.

l

Static discharge precautions should be taken when
handling the FT2008/FT2009.

Legend

1

Stub for mounting cover (2 pcs.)

2  Shield 

terminal

3  Earth ground terminal
4  Mounting holes (8 pcs.)
5  Cable tie point
6  Breakout openings for cables (2 pcs.)
7  Holes for hanging front panel over stub (2 pcs.)
8 Dip-switch
9  Screws (2 pcs.)
10  EOL jumper
11  Connection terminals for UFP line and power supply
12  Front panel earth ground connection

Mounting instruction

1.

Break out the required cable openings (6) on the
backbox.

2.

Mark the drilling points for the 3 mounting holes (4), drill
the holes and insert the anchors (not supplied); or use
the pre drilled mounting holes for installation on a 2
gang, or 4” square standard electrical box.

3.

Pull the cables for the UFP and power supply, through
the breakout openings (6) on the backbox.

4.

Screw the backbox tightly in place.

5.

Connect the cable to the terminal (11) in accordance
with the connection diagram.

6.

Configure Dip-switch (8) and EOL jumper (10).

7.

Connect the green earth ground cable from front panel
(12) to backbox (3).

8.

Hook the front panel with the holes (7) over the stubs (1)
on the backbox.

9.

Press the front panel down over the backbox, screw (9)
upwards and fix the front panel in place.

Dip-switch

8-digit Dip-switch is used for setting address and baud rate.
The first 1-4 digits are for setting address, the 7-8 digits are
for setting UFP communication baud rate. The 5-6 digits are
reserved for future use.

Add.

Dip-switch

Baud Rate

Dip-switch

1 2 3 4

7

8

1

On Off Off Off

9600 bps

Off Off

2 Off On Off Off

19200 bps

On Off

3

On On Off Off

38400 

bps  Off

On

4  Off Off On Off

57600 bps

On

On

5

On Off On Off

6 Off On On Off
7

On On On Off

8  Off Off Off On

Technical data

FT2008

FT2009

Weight

2.646 lb

3.748 lb

Dimensions (W x H x D)
(In: inch)

8.110x7.362
x1.949

11.417x7.362
x1.949

Storage temperature

14…140 °F

Operating temperature

32…120.2 °F

Humidity

≤93% rel.

Housing

IP30

Operating voltage

24V DC Nominal

18.8…27.2V DC

Operating current

25 mA

25 mA

Activation current

65 mA

105 mA