'Network' task card
BACnet device configuration
14
338 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
14.8.3 BACnet Notification Class Element
stations contain a list of 25 pre-defined entries under 'BACnet Notification
Class element' in the detail editor. Each entry stands for a
BACnet notification
class and has one unique address and one customer text within a station. The
addresses are used in the BACnet object ID as instance numbers. The customer
text provides information on which elements of the application are represented by
this notification class. The internal assignment cannot be changed. The settings
should only be changed according to a
management station integrator's
specification, and only when the behavior of different sub-systems has to be
adapted to a superordinate system.
Address Customer text
Address
Customer text
1
Areas
14
System
2
Sections
15
UGA
3
Zones
16
4
Sensors
17
IC
5
Control groups
18
Network
6
Controls
19
BACnet client
7
Spare
20
BACnet device
8
Channels (log.)
21
Line Summaries
9
Stations
22
Section Summaries
10
Module/Submodules
23
Control Groups HVAC
11
Lines
24
Controls HVAC
12
Devices
25
Channels (phys.) HVAC
13
Channels (phys.)
Table 18: Notification classes