'Detection' task card
Neural fire detector OOHC740
11
171 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
Setting the properties of the collective detector line
1. Highlight the assigned collective detector line in the tree view.
2. Set the properties you want in the detail editor.
You will find a description of the properties in the 'Hardware' tab in the following
chapters: 'Input/output module FDCIO223 [
131]' and 'Zone module FDCI723'.
You can also set the properties in the 'Hardware' task card.
You will find more information on input / output module FDCIO223 in document
009122. See chapter 'Applicable documents'.
'Reset time'
The 'Reset time' setting in the detail editor of the 'Zone' has no influence on a
collective detector line.
See also
2
Input/output module FDCIO223 [
2
11.8 Neural fire detector OOHC740
The parameter sets influence the detection behavior of the detector. This enables
the detection behavior to be adapted to the fire phenomena and environmental
influences at the place of installation.
Regardless of the fire detection parameter sets, the CO detection behavior can be
influenced by separate parameter sets and set specifically to the environmental
influences.
You will find detailed information about the neural fire detector OOHC740 in
document A6V10305793. See chapter 'Applicable documents'.
See also
2
11.8.1 Configuring fire detection
The 'Sensor' element can be assigned to a 'Automatic zone'. To determine the
danger level, the progression of the following factors is evaluated:
●
Smoke density
●
Temperature
●
CO content, depending on the set fire parameter set
Assigning 'Sensor' to 'Automatic zone'
l
Assign the 'Automatic zone' to a 'Sensor' element of a neural fire detector /
event category 'Automatic'. Link [
Setting parameter sets
You will find additional information in the chapters 'Detector parameter sets' and
'Sensor mode with multi-sensor fire detectors [
See also
2
2