'Hardware' task card
C-NET detector line
10
122 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
In the detail editor of the assigned 'Zone', you can set level at which the base
sounder will be activated:
●
In 'PRE-STAGE' and 'MAIN STAGE'
●
Only in 'MAIN STAGE'
This setting is not possible in 'Zones' without 'PRE-STAGE'.
In addition to this setting of the base sounder, you can configure a 'Universal
sounder evac control' and assign it to a base sounder. You will find more
information on this in chapter 'Evac control group [
If both the direct activation and the control are active simultaneously with different
output modes ('Alert' and 'Evac') then the base sounder is activated with the mode
'Evac'.
'Base sounder mode'
This setting specifies in which mode the base sounder is activated:
'Alert' or 'Evac'
This setting is in reference only to direct activation, which is configured with the
property 'Direct activation of base sounder'. The mode can be set separately for an
additionally configured control.
10.3.2 Detector parameter sets
parameter sets influence the detection behavior of the
automatic fire
detector. This enables the detection behavior to be adapted to the fire phenomena
and environmental influences at the place of installation.
Examples:
●
If a fire detector is used in a production hall, a parameter set that is immune to
deceptive phenomena must be selected.
●
If the smoke detector is used in a hospital room, a parameter set that ensures
the earliest possible alarming must be selected.
Set parameter set
Figure 28: Detail editor with settings for detector parameter set
1. Select the 'Hardware' task card.
2. In the tree view, open the
'Station' > the
line card > the
loop or the
stub.
3. Open the detector.
4. Highlight the element 'Sensor'.
5. Set the desired parameter set in the detail editor.
With detectors with ASAtechnology, the parameter sets for the 'Manned
operation' and 'Unmanned operation' can be set separately. With other detectors,
you can set only one parameter set.
You will find a detailed description of the parameter sets in the documentation for
the corresponding detector.