'Hardware' task card
'Station'
10
117 | 412
Building Technologies
A6V10210424_j_en_--
Fire Safety
2018-08-29
●
'Events' tab: 'Event categories' and event texts
●
'Intervention' tab, see chapter 'Intervention concept (IC) [
●
'Buzzer' tab:
– 'Element address' and 'Customer text' of the buzzer
– The 'Disable operating terminal buzzer while Cerberus-Remote is active'
checkbox defines whether the buzzer should be switched off while
'Cerberus-Remote' is active.
●
Visibility on the event categories. Visibility is set on all event
categories as standard. Visibility can also be selected for individual event
categories:
– 'ALARMS'
–
'Pre-ALARMS'
– 'Faults'
– 'Isolations'
– 'Test messages'
–
'Technical messages'
– 'Activations'
– 'Information'
●
'Control' tab: Indicates to which events the 'Station' is assigned as a cause
element for a control in the 'Control tree'.
10.1.1 Intervention concept (IC)
The intervention concept (IC) is a standard configuration for immediate intervention
and service intervention.
Events such as a fault caused by a soiled detector are monitored during a
preconfigured period of time. If the normal operation conditions are not re-
established within this period of time, the maintenance personnel is informed
(service intervention). In this way, it is possible to rectify a fault locally before
informing the maintenance personnel.
You will find a detailed description of the intervention concept in document
A6V10210355. See chapter 'Applicable documents'.
The intervention concept verifies the following event categories:
●
'All faults'
●
'All isolations'
●
'All test messages'
●
'All technical messages'
●
'All activations'
●
'All information messages'