Switching the mains voltage to AC 115 V
5
23 | 32
Building Technologies
A6V10393194_d_en_--
Fire Safety
2018-11-05
5 Switching the mains voltage to AC 115 V
The mains voltage set in the factory is AC 230 V.
Observe the safety instructions in the 'Laying the cables and connecting the
batteries [
➙
17]' chapter.
w
The mains cable is de-energized and the network is secured against
inadvertently being switched on.
w
The wire jumper between both batteries is removed.
l
Remove the power supply.
1. Open the power supply housing.
2. Switch the jumper from position X12 = AC 230 V to position X11 = AC 115 V.
Mark the change from AC 230 V to AC 115 V on the product label as shown
below.
Jumper X12
= AC 230 V
Jumper X11
= AC 115 V
s
Power supply ( 70 W)
Typ FP2015-A1
:
P.Nr.
Rat ed volt age 115/230 V
:
Frequency: 50~60 Hz
I in 1/0.5 A
:
Out put 70 W
:
ES
:
DO NOT OPEN COVER
Siemens Sw it zerland Lt d Count ry of Origin: China
X2
X1
Akku
- +
- +
Usys
M
ain
N
ot
U
se
d
B
at
te
ry
N
L
!
N
ot
U
se
d
Select ed volt age
230 V
115 V
X
:
S54400-B121-A1
Cont rol Code
:
XXYZWWW
EN54-4
VdS: G213083
0786-CPR-21302
Select ed volt age
230 V
115 V
X
X