Siemens FN2006-U1 Скачать руководство пользователя страница 15

FCC Statement 

15

Siemens Industry, Inc. 

 

A6V10315048_b_en_US

Building Technologies Division 

 

01/13/2012

 

2

 

FCC Statement 

 

WARNING 

 

Installation and usage of equipment is not in accordance with instructions manual 
Radiation of radio frequency energy 
Interference to radio communications 
●  Install and use equipment in accordance with instructions manual. 

●  Read the following information. 

This equipment generates, uses, and can radiate radio frequency energy and if not 

installed and used in accordance with the instructions manual, may cause interference 

to radio communications. 
It has been tested and found to comply with the limits for a Class A computing device 

pursuant to Part 15 of FCC Rules, which are designed to provide reasonable protection 

against such interference when operated in a commercial environment. 
Operation of this equipment in a residential area is likely to cause interference in which 

case the user at his own expense will be required to take whatever measures may be 

required to correct the interference. 

Содержание FN2006-U1

Страница 1: ...A6V10315048_b_en_US Siemens Industry Inc 01 13 2012 Building Technologies Division FN2006 U1 FN2007 U1 Fiber network module SM Fiber network module MM Mounting Installation MP UL 1 0 ...

Страница 2: ...f this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Industry Inc Building Technologies Division 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 5...

Страница 3: ...12 Table of contents 1 Fiber network module FN2006 FN2007 4 1 1 Description 4 1 2 Installation 5 1 3 Views 6 1 4 Pin assignments 7 1 4 1 Wiring 7 1 4 2 Power supply sockets 4 6 11 1 4 3 Sockets for FCnet C WEB circuits 7 8 12 1 5 Indicators 13 1 6 Technical data 14 2 FCC Statement 15 ...

Страница 4: ...tection panels to the system bus FCnet SAFEDLINK or C WEB SAFEDLINK over large distances using glass fiber optic cable The fiber network modules have the following features Fiber network module SM FN2006 Single mode transmission up to 131000 ft Fiber network module MM FN2007 Multi mode transmission up to 13100 ft Two independent electrically isolated channels SC connections for fiber optic cable G...

Страница 5: ...2007 Each fiber network module is supplied with a set of plugs 4 1 2 3 Installing the fiber network module FN2006 or FN2007 in the enclosure 2HU 1 3x fixing screw 2 Fiber network module 3 3x fastening tab on enclosure underside of fiber network module 4 3x threaded sleeve in back box 1 Position the fiber network module 2 on the back box of the enclosure as shown 2 Screw the fiber network module 2 ...

Страница 6: ...he fiber network module from above and the side 1 Fiber optic SC connection for circuit 1 2 Fiber optic SC connection for circuit 2 3 10 LED indicators for data transmission errors and power supply for both channels 4 Power B socket redundant power supply and error contact 5 Fastening tab for enclosure installation 6 Power A socket power supply and error contact 7 Socket A2 B2 FCnet C WEB circuit ...

Страница 7: ...led in the panel the relay contacts for supply supervision do not have to be connected because the panel s power supply is already supervised Power A and Power B inputs can only be supplied by UL 864 approved regulated power sources Periphery board FCI2016 FCI2017 X1001 DC 24 V AUX PAD 3 4 FN2006 FN2007 A1 B1 A2 B2 Line 1 Line 2 Power A Power B Circuit 1 NC NO C NC NO C X1001 24 V AUX Fire control...

Страница 8: ... the other device Circuit 1 must always be connected with circuit 2 The bending radius of the fiber optic cable must not be less than that specified by the manufacturer e g 10 x outer diameter Class A style 7 circuit FN2006 FN2007 FN2006 FN2007 FN2006 FN2007 Line 1 Line 2 A1 B1 A2 B2 A1 B1 A2 B2 A 1 A 1 A2 B2 A1 B1 A 1 3 3 3 Line 2 Line 1 Line 1 Line 2 Power A Power B Power A Power B Power A Power...

Страница 9: ...B1 A2 B2 A2 B2 A1 B1 FN2006 FN2007 A2 B2 A1 B1 1 3 Line 2 Line 1 Power A Power B A2 B2 A1 B1 A Class B optical network Class B optical network Wiring example of optical network class B with four fiber network modules Designation Description A Panel with installed fiber network module 1 Network module SAFEDLINK main module 3 Power A supply input A to fiber network module A1 B1 Electric FCnet C WEB ...

Страница 10: ...e network module SAFEDLINK FN2001 in the corresponding description Electrical FCnet C WEB supply line shielded or unshielded If the supply line is shielded cable glands must be used for the network module SAFEDLINK You will find information about this in the description of the network module SAFEDLINK Ground faults detected at 1 kΩ Total length of electrical FCnet C WEB wiring Max 3300 ft Each pai...

Страница 11: ...board 2 DC 24 V Supply input of DC 24 V AUX from periphery board 3 COM Common contact 4 NO Normally open 5 NC Normally closed Admissible cable cross section 16 28 AWG When installing in the fire control panel the power supply does not have to be supervised or routed redundantly The supply line for a remote network module must be shielded In the event of an error relay contacts COM and NC are conne...

Страница 12: ...network module The total cable length of the electrical FCnet C WEB connections copper cable in the optical network must not exceed 3300 ft Connection bush A1 B1 Pin Designation Description 3 B1 FCnet C WEB circuit 1 2 NC Do not use 1 A1 FCnet C WEB circuit 1 Admissible cable cross section 16 28 AWG Connection bush A2 B2 7 8 Pin Designation Description 3 B2 FCnet C WEB circuit 2 2 NC Do not use 1 ...

Страница 13: ...een Receiving data from fiber optic circuit 2 Lit up Data is being received from circuit 2 On Normal operation feeding voltage available Power B Green Supervision of feeding voltage for Power B Off No feeding voltage or voltage below minimum input voltage 9 V On Normal operation feeding voltage available Power A Green Supervision of feeding voltage for Power A Off No feeding voltage or voltage bel...

Страница 14: ...witching current DC 1 A Fibre optic cable Type of connection SC connector Wavelength 1310 nm for MM and SM Multi mode Range Fiber type 62 5 125 µm 13 100 ft Fiber type 50 125 µm 6550 ft Optical budget Fiber type 62 5 125 µm 11 dBm Fiber type 50 125 µm 7 5 dBm Single mode Range Fiber type 9 125 µm 131 000 ft Optical budget Fiber type 9 125 µm 29 dBm Minimum optical attenuation corresponds to a mini...

Страница 15: ...and can radiate radio frequency energy and if not installed and used in accordance with the instructions manual may cause interference to radio communications It has been tested and found to comply with the limits for a Class A computing device pursuant to Part 15 of FCC Rules which are designed to provide reasonable protection against such interference when operated in a commercial environment Op...

Страница 16: ...on 8 Fernwood Road Florham Park NJ 07932 Tel 1 973 593 2600 www sbt siemens com FIS 2011 Siemens Industry Inc Technical specifications and availability subject to change without notice Document ID A6V10315048_b_en_US SAP order no A5Q00050754 Edition 01 13 2012 ...

Отзывы: