Floor repeater display FT2011
40
Adjustment elements
229
Building Technologies
008837_q_en_--
Fire Safety
14.05.2012
4
3
6
5
X101
8
7
AC+
2
1
LINE+
LINE-
LINE+
LINE-
AC-
-
+
+
-
DC+/AC
DC-/AC
+
-
+
-
+
-
40.4
Adjustment elements
DIP switch
S14
Des.
Function
Position Meaning
1
3TE_OFF
Acoustic signaling in case of failure of
the FDnet supply and external supply
ON
Acoustic signaling deactivated
OFF
Acoustic signaling activated (ex-
works default setting)
2
WD_OFF
No function; switch must always be in
position 'OFF'.
OFF
Factory setting