Document No. 563-002

Installation Instructions

October 1, 2005

24 V-AC

C

E

H

C H

DO 1 DO 2 DO 3 DO 4 DO 5
NO C NO C NO C NO C NO C

DO 6 DI  3 DI  2

FLN

TRUNK

NO C AI  3

TX RX + - S BST

RTS

1   2   3   4   5   6   7   8   9  10 11 12 13 14 15 16

1   2   3   4   5   6   7   8   9  10 11 12 13 14 15 16

WL

AN0004R1

TEC Power

(From Transformer)

TEC

(Typical)

Channel

Network I.D.

24 Vac 1.2 VA

24 Vac

Power Line

18 (457)

Maximum

Alternate

Power

3M Scotchlok

TM

Power Connectors (Typical of 2)

1. Thread TEC power

wire through
connector.

2. Fold up flap to

lock TEC wire
into connector.

3. Insert power wire

from TTX into
connector so it
appears in window.

4. Use lineman’s

pliers to pinch
connecting bar in 
place and connect
wires internally.

5. Close connector

cover to secure
wires.

TEC

Power Wire

TTX

Power Wire

Figure 4.

FLNX Communication and Power Wiring.

5.

For Remote Mount Antenna:

Locate the liquid

tight

fi

tting so that the antenna extension cable

does not incur excessive pull force. At the desired
enclosure location, punch a 1/2” knockout and
use the locknut to secure the body of the liquid
tight

fi

tting into the knockout.

6.

For Remote Mount Antenna:

Route the

antenna through the body of the liquid tight

fi

tting

(Figure 5). Hand-tighten the liquid tight

fi

tting nut

to secure the antenna in place.

Make certain the liquid tight

fi

tting nut

tightens on the antenna base (Figure 5)
and not the antenna so that the antenna
can be articulated.

7. Connect the antenna wire to the FLNX.
8. Position the antenna in a vertical orientation (up

or down).

CAUTION:

For Factory installations

: The antenna

must be protected during shipment to avoid
damage to the antenna.

The installation is complete.

WL

AN0005R1

Liquid Tight Fitting

Installed in

Enclosure Knockout

Liquid Tight Fitting

Threaded Body

Antenna

Base

Antenna

Liquid Tight Fitting Locknut

Antenna Cable 12 inches

(305 millimeters)

Liquid Tight

Fitting Nut

Figure 5.

Remote mount antenna.

Siemens Building Technologies, Inc.

Page 3 of 4

Содержание FLNX

Страница 1: ...e 14 Comm recommended for Factory Mounting Warning Caution Notations WARNING Personal injury loss of life may occur if you do not follow the procedures as specified CAUTION Equipment damage or loss of data may occur if you do not follow the procedures as specified Expected Installation Time 5 minutes Tools Electro Static Discharge wrist strap Small flat blade screwdriver Cordless drill driver set ...

Страница 2: ...tenna is brought through a 1 2 knockout Figure 3 The antenna extension cable 12 long WLAN0016R1 Figure 3 Mounting Inside Enclosure Installation 1 Determine the optimal location of the FLNX and antenna for RF communications 2 Mount the FLNX using screws double sided tape or velcro included 3 Connect the communication port of the FLN device to the FLNX 4 Connect 24 Vac power Figure 4 Page 2 of 4 Sie...

Страница 3: ... so that the antenna extension cable does not incur excessive pull force At the desired enclosure location punch a 1 2 knockout and use the locknut to secure the body of the liquid tight fitting into the knockout 6 For Remote Mount Antenna Route the antenna through the body of the liquid tight fitting Figure 5 Hand tighten the liquid tight fitting nut to secure the antenna in place Make certain th...

Страница 4: ...aving a maximum gain of 5dBi Antenna having a higher gain is strictly prohibited per regulations of Industry Canada The required antenna impedance is 50Ω To reduce potential radio interference to other users the antenna type and its gain should be so chosen that the equivalent isotropically radiated power EIRP is not more than that required for successful communication The Wireless Field Level Net...

Отзывы: