Fault Diagnostics
25
Building Technologies
FL-III Maintenance and Repair
CPS Fire Safety
08.2012
4.2.2 Errors
Name
System
address
point
Description Troubleshooting
System fault
101
Triggered by any
controller fault, fibre
break, measurement
stopped or power off.
Check further error messages to analyse the
issue.
Configuration error
102
Configuration is not
loaded by the controller.
Maybe out of memory.
Repeat commissioning with reduced number of
zones and/or use alarm parameter sets with
shorter time intervals. If necessary, send
diagnosis data to technical support.
Fibre break
103
Unexpected change of
the sensor cable length.
Check the sensor cable for fibre breaks and
repair it (see Installation Manual).
Measurement error
104
Invalid measurements.
Maybe the fibre was
broken or disconnected
during measurement.
Check fibre. Repeat measurement and/or
commissioning. Send the support information
to the technical support department, if
required.
Device error,
call support
105
Controller hardware
error. Requires support
by the technical support
department.
Send the support information to the technical
support department.
Device error
106
Controller error, e.g. the
buffer battery has been
drained or faulty
installation of interface
cards.
Switch the controller off. In the case of a
drained buffer battery, replace it and repeat the
commissioning. In the event the interface
cards were not properly installed, check the
correct order of the arrangement and repeat
the commissioning. Send the support
information to the technical support
department, if required.
Environmental
conditions error
107
Supply voltage,
temperature and / or
moisture are outside of
the permissible range.
Provide environmental conditions in
accordance with the specifications. Improve
the air circulation around the controller.
Handling error
108
No fibre connected or
the connected fibre is
too short or too long.
Check whether a fibre-optical connector is
connected. Check the length of the sensor
fibre (at least 100 m, not longer than 100 m of
the range of the controller). Check the sensor
fibre for possible fibre breaks. Check the
configuration of the controller.
Measurement
stopped
109
Message sent once
when the measurement
is stopped.
Start measurement if required.
Measurement
inactive
110
Periodic message when
the measurement is
inactive.
Start measurement if required.
Tab. 6
Error messages / recommendations for troubleshooting