Maintenance
10
Building Technologies
FL-III Maintenance and Repair
CPS Fire Safety
08.2012
3 Maintenance
3.1 General
The controller has been developed in such a manner that maintenance is not
required outside of the scheduled maintenance intervals. The functions are
monitored internally by means of safety circuits and software routines. Malfunctions
are reported automatically and are indicated by means of light-emitting diodes
(LED’s) on the front of the device. Irrespective of this, annual functional tests are
required in order to ensure the correct function in accordance with the technical
safety requirements. The maintenance work requires an operational controller
without error messages.
Additional testing or shorter maintenance intervals may be required due to national
legislative and normative requirements as well as an increased requirement with
regard to safety.
The FibroManager is used to read out the event memory, the status report and
the support information of the controller BEFORE and AFTER the work and
these must be stored for documentary purposes.