Specifications
26
Building Technologies
A6V10201150_a_en_--
Fire Safety & Security Products
05.06.2008
8
Specifications
8.1
Technical data
Detector line
Operating voltage
16 … 26 V DC
Quiescent current
0.01 mA
Alarm current (permanent, maximum)
60 mA
Alarm current (pulsating)
100 mA
Maximum current connection factor
1
Quiescent current connection factor
1
Protocol
collective (SynoLINE600)
Compatibility
Refer to document 'List of compatibility' (doc.
no. 008331)
Detector line:
z
Design
Screw terminals
Connections
z
Wire cross-section
0.28 … 1.5 mm
2
Environmental conditions
Operating temperature
-25 … +70 °C
Storage temperature
-30 … +75 °C
Air humidity
≤95 % rel.
Protective category
IP44
Electromagnetic compatibility at:
z
10 MHz … 1 GHz
50 V/m
z
1 GHz … 2 GHz
10 V/m
Mechanical data
Dimensions (L x W x H):
z
FDM1101-Rx
87 x 87 x 20 mm
z
FDM1101-Rx with back box
FDMH295-R / FDMH295-S
87 x 87 x 53 mm
Weight:
z
FDM1101-Rx
0.097 kg
z
Back box FDMH295-R / FDMH295-S 0.057 kg
Colors:
z
FDM1101-Rx
red (RAL 3000)
z
Back box FDMH295-R / FDMH295-S red (RAL 3000)
Material
ABS PC ASA