background image

Building Technologies

 

 

A6V10214524_a_en_-- 

Fire safety and security products 

 

03.2010 

 

 

Application 

l

 

Protection of different branches from breaking down at the same time due to a short 
circuit. 

l

 

In a loop line connection, up to 32 devices can be connected between two isolators. 

l

 

In a stub line connection, up to 32 devices can be connected to one isolator. 

 

 

Structure 

The module consists of the module carrier, the printed circuit board and the cover. The 
printed circuit board includes two LEDs to indicate isolating/localization status.   
 
To protect the modules from environmental influences, housing FDCH221

 

is optional

 

 

 

                                Fig.1 Overview 
 

Содержание FDCL181

Страница 1: ...ches of FD18 BUS l Indication of conditions by LED indicator l Automatic address setting without encoder settings or Dip switch l Communication via FD18 BUS separate address l Directly applicable in dry areas Applicable in humid and dusty areas with a housing l Sticker Method easy for commissioning Function l Embedded in a FD18 BUS same function as a electronic switch to isolate the short circuit ...

Страница 2: ...ction up to 32 devices can be connected between two isolators l In a stub line connection up to 32 devices can be connected to one isolator Structure The module consists of the module carrier the printed circuit board and the cover The printed circuit board includes two LEDs to indicate isolating localization status To protect the modules from environmental influences housing FDCH221 is optional F...

Страница 3: ...CH221 Installation of FDCH221 Housing 1 Open the housing 2 Determine the cable entries in the housing and break these open 3 Use two screws M 4 to fit the housing on a plane surface Fig 3 Distance between holes 182 0 1 0mm 4 Fix and guide in the cables with waterproof joint provided by users themselves 5 Fix the lid additionally with four screws Fig 4 Only this way is IP protection guaranteed The ...

Страница 4: ...10 48 Specification Operating voltage 12 32VDC Operating current Quiescent 0 25 mA Activation current 0 45 mA Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 Communication protocol FD18 BUS Connection terminal 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With housing FDCH221 IP65 Details for ordering Type Material No P...

Отзывы: