End of Line Resistor Wiring Overview

CAUTION: FOR SYSTEM SUPERVISION – FOR TERMINALS IDENTIFIED WITH A

 DO NOT USE

LOOPED WIRE TERMINALS. BREAK WIRE RUN TO PROVIDE SUPERVISION OF CONNECTIONS.

Use Siemens TB-EOL terminal P/N S54322-F4-A2 or equivalent.

Use only normally open dry contact SWITCHES for the inputs

Figure 11  Wiring end of line and switch

·

Use a 4 or 2 pole UL/ULC recognized SWITCH.

·

Switch Terminal must be capable of two conductors at one terminal.

·

EOL Resistor wiring must be done according to UL 864 and ULC-S527, chapter ‘EOL Devices’.

·

The EOL Resistors must be connected at the end of the input lines.

·

No addressable device or 2-wire smoke detectors can be connected to the inputs.

ACCESSORIES

DEVICE

ORDER NO.

EOL resistor 100

±1% ½ W

S54312-F7-A1

SIEMENS INDUSTRY, INC.

4

11

/

16

-inch adapter plate (optional)

M-411000

RANDL INDUSTRIES, INC.

5-inch Box (optional)

T55017

RANDL INDUSTRIES, INC.

5-inch Box (optional)

T55018

RANDL INDUSTRIES, INC.

5-inch Box (optional)

T55019

RANDL INDUSTRIES, INC.

TB-EOL terminal

S54322-F4-A2

SIEMENS INDUSTRY, INC.

SHIELDED W IRE MAX: 200 FT
18 - 14 AWG
OPEN AND SHORT SUPERVISION

OPEN

CLASS B STYLE C,   OPEN AND SHORT WIRING SUPERVISION

SHIELDED W IRE MAX: 200 FT
18 - 14 AWG

OPEN SUPERVISION

OPEN

IN1 - 4

IN1 - 4

X

EARTH
GND

CLASS A STYLE D,   OPEN WIRING SUPERVISION

CAUTION: BE AWARE OF THE INPUT POLARITY IN CLASS A MODE

SHIELDED W IRE MAX: 200 FT
18 - 14 AWG

OPEN

OPEN

X

EARTH
GND

CLASS B STYLE B,   OPEN WIRING SUPERVISION

OPEN SUPERVISION

X

EARTH
GND

470 

Ω

100 

Ω

470 

Ω

470 

Ω

for UL:

 mount EOL directly on the last SWITCH terminal

for ULC:

 mount EOL on the TB-EOL terminal

TB-EOL

TB-EOL

SW ITCH

SW ITCH

SW ITCH

  

SW ITCH

Содержание FDCIO422

Страница 1: ...ing type form A relay contacts for fire control installations Status indication per LED for each input and output plus 1 LED for general status of the device Power supply via FDnet supervised power limited Including 4 EOL devices 470 Ω 3 separators to separate the power limited wiring from the non power limited Separators are delivered in 3 different sizes for standard 4 11 16 inch box 4 11 16 inc...

Страница 2: ...se follow the corresponding description of the Panel used WIRING Refer to Figure 11 Refer to the appropriate wiring diagram and wire the addressable input output module accordingly Recommended wire size 18 AWG minimum and 14 AWG maximum Wire larger than 14 AWG can damage the connector Refer to Figures 2 and 3 Follow the instructions in the DPU manual or 8720 manual to program the FDCIO422 to the d...

Страница 3: ...n power limited fire protection signaling conductors For the FDCIO422 wiring to the terminal block for line and inputs must enter the outlet box separately from the terminals for outputs For the output terminals protection with a fuse is recommended Refer to Figures 6 and 9 WIRING AT THE TERMINAL BLOCKS Minimize the length of wire entering the outlet box Figure 6 Power Limited Wiring Separators Th...

Страница 4: ...se the module without the faceplate Remove the faceplate for service and maintenance reasons only Figure 7 Mounting the FDCIO422 TECHNICAL DATA Operating voltage DC 12 32 V Operating current quiescent 1 mA Absolute maximum peak current 1 92 mA Maximum current connection factor 2 4 Relays output 1 normally open normally closed DC 30 V AC 125 V Max 4x 5 A or 2x 7 A OUT B C or 1x 8 A OUT C Operating ...

Страница 5: ...ptable means Insulate shields do not make any connections to the device or back box 16 Use shielded and or twisted wire to connect the switch wiring and keep the wiring as short as possible 17 Tie the switch wiring shield to the local earth ground at only one end refer to Figure 9 For multiple switches on the same input connect incoming and outgoing shields together in an acceptable means Insulate...

Страница 6: ...l Remedy cause Note Any general message can be displayed together with another status Configuring the outputs Configuring the inputs For configuring the outputs proceed as follows a Determine in which position the contact is active The contact can be active when it is Closed normally open NO Open normally closed NC b After activating the contact remains Permanently active Active only for a certain...

Страница 7: ...10 FDCIO422 input wiring Class A and Class B for details of Line 1 and 2 wiring see Figure 8 for details of the input wiring see Figure 11 OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D OUT A OUT B OUT C OUT D 470 1 W Ω Rs Rp Rp please order separately ORDER NO S54312 F7 A1 100 1 W Ω ONLY OPEN MONITORING ONLY OPEN MONITORING a b a b a b a b a b a b a b a b a b a b a b a b UL864 CLASS STYLE B B UL...

Страница 8: ...27 chapter EOL Devices The EOL Resistors must be connected at the end of the input lines No addressable device or 2 wire smoke detectors can be connected to the inputs ACCESSORIES DEVICE ORDER NO EOL resistor 100 Ω 1 W S54312 F7 A1 SIEMENS INDUSTRY INC 4 11 16 inch adapter plate optional M 411000 RANDL INDUSTRIES INC 5 inch Box optional T55017 RANDL INDUSTRIES INC 5 inch Box optional T55018 RANDL ...

Отзывы: