background image

Building Technologies

 

 

A6V10214492_a_en_-- 

Fire safety and security products 

 

03.2010 

 

 

Dry contact output  

Potential-free contact (Output not monitored) 

-

 

Be used for controlling (e.g. closing a door). 

-

 

Output control is not monitored.  

-

 

An externally supplied 24 V DC voltage is not needed. 

-

 

The jumper on the input/output module must be plugged onto J1/J3 (Fig. 6). 

 

     

 

Fig.6 Input/output module jumper position J1 

 

Fig. 7 Connection diagram for potential-free contact output 

Configuration 

The following configurations are possible by controller or configuration tools : 

l

 

The contact is active, when: 

 

Normal mode: normally open NO closes 

 

Inverted mode: normally closed NC opens 

l

 

After activating the output remains: 

 

Steady output 

 

Pulse output: How long the contact remains active can be configured by controller or 
configuration tools (pulse duration). 

l

 

Failsafe behavior when the FD18-BUS detector line is current-free or in degraded mode. 
The error behavior defines the position of the output through controller or configuration 
tools in case of an error: 

 

Off: Output remains in the same position as before the error 

 

Activation: Output is activated in case of an error 

 

Deactivation: Output is deactivated in case of an error 

 

The controller does not monitor external equipment status (activated/inactivated). 

Structure 

The module consists of the module carrier, the printed circuit board and the cover. The printed 
circuit board includes the LEDs. The LEDs indicate the states of the inputs/outputs. The cover 
of the printed circuit board is transparent, so that the state of the LEDs is visible even when 
the housing is closed.  
To protect the modules from environmental influences, housing FDCH221 is optional. 

Содержание FDCIO181-2

Страница 1: ...s monitored for open line or short circuit l Prevention of noise interference through intelligent analysis of input signals l Output lines monitored for open line or short circuit when potential output and not activated l Output monitoring configurable on off l Control output for equipment 24 VDC max 2 A l Power supply via FD18 BUS l Communication with controller via FD18 BUS detector line l Direc...

Страница 2: ...ted Line monitoring and circuitry The input lines are monitored for open line or open line and short circuit To make these possible resistors must be properly connected to the end of lines of the input Fig 1 When an open line or a short circuit occurs on one of the input lines a fault message is transmitted to the control panel The input must be potential free Output External power output Default ...

Страница 3: ...must be plugged onto J2 J4 Fig 4 Fig 4 Input output module jumper position J2 J4 Fig 5 Connection diagram for inverted operation e g when used as door retainer In inactive status the 24 V DC are permanently applied to the output and may keep a door open for example When the output is switched to active the output goes into open status no 24 V DC voltage and the door is closed Comment In this examp...

Страница 4: ...ct remains active can be configured by controller or configuration tools pulse duration l Failsafe behavior when the FD18 BUS detector line is current free or in degraded mode The error behavior defines the position of the output through controller or configuration tools in case of an error Off Output remains in the same position as before the error Activation Output is activated in case of an err...

Страница 5: ...for the connection of the FD18 BUS detection line 9 Connection input 1 10 Connection input 2 Jumper Jumper position Signification Output1 is not monitored Output1 is monitored factory default Output2 is not monitored Output2 is monitored factory default If the configurations on the control panel and jumper don t match this is recognized and an error message is triggered Any other jumper position i...

Страница 6: ...n the housing 5 Insert the seal and fix the lid additionally with four screws Fig 11 only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Procedure with installation in the housing CAUTION Overheating of the in output module 1 Open the housing 2 Place the module in the h...

Страница 7: ...ng current quiescent 0 56 mA Activation current 0 85 mA Output Capacity Resistor Diode 2 A 24 VDC 3 3k Ω 1N5404 Input Resistor 3 3k Ω 680 Ω Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 rel Communication protocol FD18 BUS Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With FDCH221 housing IP65 Deta...

Отзывы: