FDCIO181-2 Input/Output Module 
Product Manual 

 

 
 
 
 

Characteristic 

 

l

 

Microprocessor-controlled signal evaluation 

l

 

Automatic address setting, without encoder settings or DIP switch 

l

 

2 monitored input, 2 monitored output 

l

 

LED display of input and output status 

l

 

Input lines monitored for open line or short circuit 

l

 

Prevention of noise interference through intelligent analysis of input signals 

l

 

Output lines monitored for open line or short circuit (when potential output and not activated) 

l

 

Output monitoring configurable(on/off) 

l

 

Control output for equipment 24 VDC, max. 2 A 

l

 

Power supply via FD18-BUS 

l

 

Communication with controller via FD18-BUS(detector line) 

l

 

Directly used in dry areas. Applicable in dusty and humid areas when installed in housing 

l

 

Sticker Method

 easy for commissioning 

Содержание FDCIO181-2

Страница 1: ...s monitored for open line or short circuit l Prevention of noise interference through intelligent analysis of input signals l Output lines monitored for open line or short circuit when potential output and not activated l Output monitoring configurable on off l Control output for equipment 24 VDC max 2 A l Power supply via FD18 BUS l Communication with controller via FD18 BUS detector line l Direc...

Страница 2: ...ted Line monitoring and circuitry The input lines are monitored for open line or open line and short circuit To make these possible resistors must be properly connected to the end of lines of the input Fig 1 When an open line or a short circuit occurs on one of the input lines a fault message is transmitted to the control panel The input must be potential free Output External power output Default ...

Страница 3: ...must be plugged onto J2 J4 Fig 4 Fig 4 Input output module jumper position J2 J4 Fig 5 Connection diagram for inverted operation e g when used as door retainer In inactive status the 24 V DC are permanently applied to the output and may keep a door open for example When the output is switched to active the output goes into open status no 24 V DC voltage and the door is closed Comment In this examp...

Страница 4: ...ct remains active can be configured by controller or configuration tools pulse duration l Failsafe behavior when the FD18 BUS detector line is current free or in degraded mode The error behavior defines the position of the output through controller or configuration tools in case of an error Off Output remains in the same position as before the error Activation Output is activated in case of an err...

Страница 5: ...for the connection of the FD18 BUS detection line 9 Connection input 1 10 Connection input 2 Jumper Jumper position Signification Output1 is not monitored Output1 is monitored factory default Output2 is not monitored Output2 is monitored factory default If the configurations on the control panel and jumper don t match this is recognized and an error message is triggered Any other jumper position i...

Страница 6: ...n the housing 5 Insert the seal and fix the lid additionally with four screws Fig 11 only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Procedure with installation in the housing CAUTION Overheating of the in output module 1 Open the housing 2 Place the module in the h...

Страница 7: ...ng current quiescent 0 56 mA Activation current 0 85 mA Output Capacity Resistor Diode 2 A 24 VDC 3 3k Ω 1N5404 Input Resistor 3 3k Ω 680 Ω Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 rel Communication protocol FD18 BUS Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With FDCH221 housing IP65 Deta...