FDCIO181-1 Input/Output Module
Product Manual

Characteristic

l

Microprocessor-controlled signal evaluation

l

Automatic address setting, without encoder settings or DIP switch

l

1 monitored input, 1 monitored output

l

LED display of input and output status

l

Input lines monitored for open line or short/open circuit

l

Prevention of noise interference through intelligent analysis of input signals

l

Output lines monitored for open line or short/open circuit (when potential output not
activated)

l

Output monitoring configurable(on/off)

l

Control output for equipment 24 VDC, max. 2 A

l

Communication with controller via FD18-BUS(detector line)

l

Directly used in dry areas. Applicable in dusty and humid areas when installed in FDCH221
housing

l

“Sticker Method” easy for commissioning

Application

Input

With the input a status can be monitored, the input can be configured by controller or
configuration tools as follows:

l

Status

 input or

Alarm

 input

l

Lead monitoring for open line or open line and short circuit

l

When inputting status, according to different status of contact, can be set as fallows:

–  Normal mode: normally open NO input
–  Inverted mode: normally closed NC input

Fig. 1 connection diagram of dry contact input

Содержание FDCIO181-1

Страница 1: ...ot activated l Output monitoring configurable on off l Control output for equipment 24 VDC max 2 A l Communication with controller via FD18 BUS detector line l Directly used in dry areas Applicable in dusty and humid areas when installed in FDCH221 housing l Sticker Method easy for commissioning Application Input With the input a status can be monitored the input can be configured by controller or...

Страница 2: ...onto J2 Fig 2 Fig 2 Input output module jumper position J2 Fig 3 Connection for normal operation with output line monitored for short circuit and open line Configuration The following configurations are possible through controller or configuration tool l After activating the output remains Steady output Pulse output How long the contact remains active can be configured by controller or configurati...

Страница 3: ...put How long the contact remains active can be configured by controller or configuration tools pulse duration l Failsafe behavior when the FD18 BUS detector line is current free or in degraded mode The error behavior defines the position of the output through controller or configuration tools in case of an error Off Output remains in the same position as before the error Activation Output is activ...

Страница 4: ...activated in case of an error Deactivation Output is deactivated in case of an error The controller does not monitor external equipment status activated inactivated Structure The module consists of the module carrier the printed circuit board the cover and the protection cover The printed circuit board includes the LEDs The LEDs indicate the states of the inputs outputs The cover of the printed ci...

Страница 5: ... surface with two screws Fig 10 Distance between holes 182 0 1 0mm 4 Insert the cables and fix the cables in the housing 5 Insert the seal and fix the lid additionally with four screws Fig 11 only this way is IP65 protection guaranteed The housing lid is transparent Consider a suitable installation position to make sure that the LEDs of the module are visible at any time Procedure with installatio...

Страница 6: ...nt 0 51 mA Output Capacity Monitoring resistor Diode 2 A 24 VDC 3 3k Ω 1 4w 1N5404 Input Monitoring resistor 3 3k Ω 680 Ω Operating temperature 0 42 C Storage temperature 20 75 C Humidity 95 rel Communication protocol FD18 BUS Load factors 3 Connection terminals 1 0 1 5 mm2 Color Housing Cover white RAL 9010 transparent Protection category EN60529 IEC529 GB4208 93 With FDCH221 housing IP65 Details...