Siemens FDB271 Скачать руководство пользователя страница 1

FDOOT271, FDB271

Radio fire detector, detector base

Mounting

A6V10227637_j_en_--

Smart Infrastructure

2020-03-31

Содержание FDB271

Страница 1: ...FDOOT271 FDB271 Radio fire detector detector base Mounting A6V10227637_j_en_ Smart Infrastructure 2020 03 31 ...

Страница 2: ...thorization are prohibited Offenders will be held liable for payment of damages All rights created by patent grant or registration of a utility model or design patent are reserved Issued by Siemens Switzerland Ltd Smart Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug Tel 41 58 724 2424 www siemens com buildingtechnologies Edition 2020 03 31 Document ID A6V10227637_j_en_ Siemens Sw...

Страница 3: ...e FDBZ291 11 2 6 Detector dust cap FDZ291 12 2 7 Detector base seal RS720 13 2 8 Establishing factory settings 14 3 Details for ordering 15 3 1 Radio fire detector FDOOT271 15 3 2 Detector base FDB271 15 3 3 Battery pack BAT3 6 10 15 3 4 Detector locking device FDBZ293 16 3 5 Designation plate FDBZ291 16 3 6 Detector dust cap FDZ291 16 3 7 Detector base seal RS720 17 4 Specifications 18 4 1 Techni...

Страница 4: ...4 22 A6V10227637_j_en_ ...

Страница 5: ... documents Document ID Title 001508 Guidelines Connection factors line resistances and capacitances for fire detection systems collective AnalogPLUS interactive FDnet 008331 List of compatibility for Sinteso product line 009409 Data sheet Colored detectors bases and base attachment FDO FDOOT FDT FDB FDCW241 010030 Application guideline Sinteso Fire detectors A6V10208552 Installation Detector locki...

Страница 6: ...e installation position take into account any structures that may impair radio reception There must be at least 50 cm of free space below and at least 2 cm to the sides of the detector so that the detector can be removed with the detector exchanger Contorted detector bases complicate or even impede the insertion of the detectors with the detector exchanger min 2 cm min 50 cm Figure 1 Minimum spaci...

Страница 7: ...w the detector base securely onto the substructure using two screws 2 2 1 1 2 4 2 3 46 mm 90 mm Figure 2 Mounting the detector base 1 Detector base 2 Screws with max Ø of 4 mm 3 Holder for detector locking device 4 Switching cam Mounting Installation Detector base FDB271 2 A6V10227637_j_en_ 7 22 ...

Страница 8: ...very The flashing behavior of the internal alarm indicator is described in the Internal alarm indicator chapter w The radio gateway has been activated and switched to maintenance mode w The radio fire detector is set to the factory settings 14 w You have the battery pack and the required accessories to hand w The detector base FDB271 is mounted 7 1 Install the accessories you require 2 Label the n...

Страница 9: ... detector has already been logged on to a radio gateway a If this does not happen this means the battery pack is defective and must not be used 6 Insert the radio fire detector into the detector base a The internal alarm indicator flashes green and the radio fire detector is logged on to the radio gateway a If the process of logging on to the radio gateway is successful the internal alarm indicato...

Страница 10: ...socket 5 Allen key 3 Hole 1 Place the set screw with a hexagon socket 2 in the hole 3 on the detector 4 2 Insert the detector 4 into the detector base 1 3 Using the Allen key provided 5 insert the set screw with a hexagon socket 2 through the hole in the detector base 1 and tighten a The detector can no longer be removed from the base without tools Mounting Installation Detector locking device FDB...

Страница 11: ...to the detector 1 Label the designation plate 2 Slide the designation plate into the detector base from the side A B 1 3 4 E FDBZ291 FDB271 1 2 Figure 5 Installing the designation plate 1 Designation plate 2 Detector base Mounting Installation Designation plate FDBZ291 2 A6V10227637_j_en_ 11 22 ...

Страница 12: ... and dirt FDZ291 1 2 3 Figure 6 Mounting removal of detector dust cap FDZ291 1 Detector 2 Detector dust cap 3 Removing detector dust cap by turning it to the right The detector dust cap can be put on or removed either manually or using the detector exchanger e g FDUD291 Mounting Installation Detector dust cap FDZ291 2 12 22 A6V10227637_j_en_ ...

Страница 13: ... detector base seal 1 NOTICE Excessively large holes in the detector base seal will impair the potential protection category Do not cut or drill holes in the detector base seal 2 Fit the detector base seal RS720 between the ceiling and the detector base or the sounder base Figure 7 Mounting detector base seal RS720 Mounting Installation Detector base seal RS720 2 A6V10227637_j_en_ 13 22 ...

Страница 14: ...detector is being supplied with power w You have a slim pen or pencil to hand 1 Remove the radio fire detector from the detector base 2 Wait until the internal alarm indicator 1 flashes green 2 second interval a The detector is out of base 3 Press the pen or pencil into the new opening 2 for 5 seconds a The internal alarm indicator flashes red 2 second interval a The radio fire detector is set to ...

Страница 15: ...d with two screws Compatible with Radio fire detector FDOOT271 Order number for FDB271 S54319 F12 A1 3 3 Battery pack BAT3 6 10 For supplying radio devices and the radio gateway with power Lithium batteries BAT3 6 10 LI SOCl2 battery pack 3 6 V 10 Ah Batteries with battery cable Connector system with protection against polarity reversal Inscription field for commissioning date Compatible with Radi...

Страница 16: ...5Q00005035 3 5 Designation plate FDBZ291 To identify the location Compatible with Detector base FDB2xx AA Detector base FDB271 Sounder base FDSB29x Base attachment FDB291 Interbase FDSB22x Base wall mounting FDB226 x Base deep wall mounting FDB227 x Sounder beacon base FDSB226 Voice sounder beacon base FDSB227 Order number A5Q00002621 3 6 Detector dust cap FDZ291 To protect the point detector from...

Страница 17: ...42 Compatible with Detector base collective DB110 Detector base collective DB110x Detector base collective DB110xx Detector base FDB271 Not compatible with Designation plate FDBZ291 Order number S54319 F8 A1 Details for ordering Detector base seal RS720 3 A6V10227637_j_en_ 17 22 ...

Страница 18: ...6b Range See document A6V10227631 COMMISSION IMPLEMENTING DECISION EU 2019 1345 of 2 August 2019 amending Decision 2006 771 EC updating harmonised technical conditions in the area of radio spectrum use for short range devices notified under document C 2019 5660 Battery pack BAT3 6 10 Lithium battery pack BAT3 6 10 LI SOCl2 battery pack 3 6 V 10 Ah Battery service life At least 3 years depending on...

Страница 19: ...Standards European standards EN 54 5 EN 54 7 EN 54 25 EN 54 29 EN 300220 2 EN 301489 3 EN 60950 1 Specifications Technical data 4 A6V10227637_j_en_ 19 22 ...

Страница 20: ...erials Use of halogen free plastics Electronic parts and synthetic materials can be separated Larger plastic parts are labeled according to ISO 11469 and ISO 1043 The plastics can be separated and recycled on this basis Electronic parts and batteries must not be disposed of with domestic waste Take electronic parts and batteries to local collection points or recycling centers Contact local authori...

Страница 21: ...A6V10227637_j_en_ 21 22 ...

Страница 22: ...t Infrastructure Global Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2012 Technical specifications and availability subject to change without notice A6V10227637_j_en_ ...

Отзывы: