Siemens Industry, Inc.
Building Technologies  Division

A6V10315044_enUS_c

3

PRE-INSTALLATION

Before connecting either the printer, power or the UFP, the network address must be
set for the FCA2018-U1 using the three-position switch. (Refer to Figure 2 for the
location of the switch.)  The address for the FCA2018-U1 must be the same as the
address selected for it in the FS20 Configuration Tool. To increment each digit of the
address, press the “+” button above the desired digit; to decrement each digit, press
the “-” button below the desired digit. The range of allowable addresses is from 001
to 8 (leading zeros must be used).

If the FCA2018-U1 is located at the end of the UFP network (Style 4 only), the termi-

nation switch must be set to ON. Otherwise it must be set to OFF.

Figure 3

Installing The  FCA2018-U1 Terminal  Block  Covers

Figure 4

Connecting The  Printer To The  FCA2018-U1

120 VAC

60 Hz.

CENTRONICS

PARALLEL

PAL-1 or EDP LISTED PRINTER

FCA2018-U1

SPP

CABLE SUPPLIED WITH FCA2018-U1

SUPERVISED

POWER LIMITED

Two terminal block covers are provided with the FCA2018-U1. Each comes as two
separate parts, a lower bracket which has a ¾ inch conduit opening and a cover.
Attach the lower bracket to each end of the FCA2018-U1 using four of the #10 nuts
provided in the FCA2018-U1 hardware kit. Reserve the covers and the remaining
hardware until the FCA2018-U1 is mounted and wired.

Mount the FCA2018-U1 to either the wall or desk where the PAL-1 is located. Use
the four mounting holes in the lower bracket.

NOTES:
1. The maximum distance from the FCA2018-U1 to the PAL-1 is 6 feet. The two modules must be in the same room.
2. For NFPA 72 Local, Auxiliary and Remote Station configurations, connect the output of the FCA2018-U1 to any

UL EDP listed printer.

3. The printer must support the EPSON FX command set.
4. For NFPA 72 Proprietary of UL 1076 configurations use printer SIEMENS Model PAL-1, a UL listed for fire Centronics parallel printer.
5. The printer is supervised for AC loss, off line, paper out, paper jam, and connection to the FCA2018-U1.
6. After loading the paper in the PAL-1 printer, turn off the power and follow the steps below.

• While pressing the LOAD PARK button, turn on the power to the PAL-1 printer. Keep pressing the LOAD PARK button for 5 seconds.
• Release the LOAD PARK button.
• The current setting will print.
• When printing is completed, the ON LINE indicator will be lit. If the ON LINE indicator is not lit, press the ON LINE button.

Содержание FCA2018-U1

Страница 1: ...terface When used in conjunction with the PAL 1 it provides a supervised logging printer meeting the requirements of NFPA 72 Proprietary or UL 1076 Security systems For NFPA 72 Local Auxiliary or Remote Station applications any UL EDP listed Centronics parallel printer may be used See notes 2 3 and 4 on Figure 3 Features FCA2018 U1 features are as follows Supervision of the PAL 1 includes paper ou...

Страница 2: ... U1 contains one reset switch three LEDs one termination switch and one UFP address switch as shown in Figure 2 A reset switch is located on the top of the panel Pushing the reset switch re initializes the FCA2018 U1 operation POWER Green Normally ON When illuminated indi cates that power for the FCA2018 U1 is applied to the module CPU FAIL Yellow Normally OFF When illuminated indi cates that the ...

Страница 3: ...ich has a inch conduit opening and a cover Attach the lower bracket to each end of the FCA2018 U1 using four of the 10 nuts provided in the FCA2018 U1 hardware kit Reserve the covers and the remaining hardware until the FCA2018 U1 is mounted and wired Mount the FCA2018 U1 to either the wall or desk where the PAL 1 is located Use the four mounting holes in the lower bracket NOTES 1 The maximum dist...

Страница 4: ...und fault detection impedance _ CHASSIS GROUND 24V INPUT 1 2 3 TO FC360 X1_N SUPERVISED POWER LIMITED TO FC360 X1_P The FCA2018 U1 can be connected to the UFP Style 6 or Style 4 Refer to the FS20 configuration for the proper Style If the FCA2018 U1 is connected at the end care must be taken to properly terminate the UFP See Figure 6 for the wiring instructions when the FCA2018 U1 is connected as S...

Страница 5: ...X2 1 RS485 AF RS485 BF RS485 AR RS485 BR DO NOT USE SUPERVISED POWER LIMITED TO NEXT UFP MODULE Figure 8 UPS Wiring Diagram 1 H 2 GND 3 N 4 H 5 N 9 H 10 GND 11 N 6 H 7 GND 8 N 120 VAC UTILITY POWER SOURCE DO NOT USE DO NOT USE POWER TO PRINTER 120 VAC SEE NOTE 4 AC INPUT FAIL TERMINAL BLOCK LOCATED ON UPS SYSTEM CONTROL BOARD TO HTRI S D R INPUT TERMINALS PROGRAM AS NORMALLY CLOSED TROUBLE CAUSING...

Страница 6: ...he FCA2018 U1 Position the FCA2018 U1 and attach it to the mounting surface using the four 6 self tapping screws provided Install the terminal block covers using the 6 remaining 10 nuts Refer to Figure 3 ELECTRICAL RATINGS 24V Back Plane Current 0 Screw Terminal 24V Current 150mA Max 6 2V Back Plane Current 0 24V Standby Current 150mA Max Output Power CAN Network Pair 8V peak to peak max 75mA max ...

Страница 7: ...Siemens Industry Inc Building Technologies Division A6V10315044_enUS_c 7 This page was left intentionally blank ...

Страница 8: ...Siemens Industry Inc Building Technologies Division Florham Park NJ Document ID A6V10315044_enUS_c This page was left intentionally blank P N A5Q00050826 ...

Отзывы: