HW configura‐
tion
Channel 1
Channel 2
Channel 3
Channel 4
Simulation value
Signal input
●
●
0 (low) or 1 (high)
Signal output
● Current
● Pulse
● Frequency
● Status
●
●
●
● 0 to 25 mA
● 0 to 12.5 kHz
● 0 to 12.5 kHz
● 0 (low) or 1 (high)
Process value simulation
The following process values can be simulated:
● Mass flow
● Volume flow
● Standard Volume flow
● Density
● Process Media Temperature
● Fraction A %
● Fraction B %
Enabling simulation for the process values sets the simulated value for all outputs.
Alarm simulation
It is possible to simulate either specific alarms (ID numbers) or alarm classes. The alarm
classes are either Siemens or NAMUR depending on the configuration of Alarm Mode, menu
item 2.8.11.
Any simulated alarms will be time-stamped 1900-01-01 00:00 if the alarms have not previously
appeared as real alarms. Any real alarms will be time-stamped with the actual date and time
of each alarm occurrence.
All alarms mentioned in Sensor diagnostic events (Page 189) can be simulated; except ID 51
(Malfunction in Pickup Amplitude) and ID 165 (Ref. density simulated).
8.16
Maintenance
● Set Date and Time
The device has a built-in real-time clock used for time stamps of various events (for example
alarms and configuration changes). The date and time can be set in menu item 3.3.2.
● Set To Default
The device can be reset to its default settings in menu item 3.3.3.
● Restart Device
The device can be restarted without disconnecting the power in menu item 3.3.4.
Functions
8.16 Maintenance
MASS 2100 & FC300 (FCT030)
166
Operating Instructions, 06/2017, A5E39789040-AA
Содержание FC300
Страница 9: ...Index 515 Table of contents MASS 2100 FC300 FCT030 Operating Instructions 06 2017 A5E39789040 AA 9 ...
Страница 10: ...Table of contents MASS 2100 FC300 FCT030 10 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 36: ...Description 3 7 Theory of operation MASS 2100 FC300 FCT030 36 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 90: ...Connecting 5 4 Device nameplates MASS 2100 FC300 FCT030 90 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 258: ...Dimension drawings 12 4 Mounting bracket MASS 2100 FC300 FCT030 258 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 478: ...Default settings B 15 Language MASS 2100 FC300 FCT030 478 Operating Instructions 06 2017 A5E39789040 AA ...
Страница 518: ...Index MASS 2100 FC300 FCT030 518 Operating Instructions 06 2017 A5E39789040 AA ...