87
Smart Infrastructure
A6V10393190_h_en_--
2019-09-01
Appendix B: Switch mains to AC 115 V
Only available for the fire control panel FC123-ZA and FC124-ZA.
Step 1: Remove power supply FP2015-A1 and open it.
Step 2: Move the jumper on the PCB board from X12 to X11.
Step 3: Mark AC 115 V with 'x' and AC 230 V with '-----' on the label as indicated below.
s
Power supply (70 W)
Typ FP2015-A1
:
P.Nr.
Rated voltage 115/230 V
:
Frequency: 50~60 Hz
I in 1/0.5 A
:
Output 70 W
:
ES
:
DO NOT OPEN COVER
Siemens Switzerland Ltd Country of Origin: China
X2
X1
Akku
- + - +
Usys
M
ain
N
ot
U
se
d
B
att
er
y
N L
!
N
ot
U
se
d
Selected voltage
230 V
115 V
X
:
S54400-B121-A1
Control Code
:
XXYZWWW
EN54-4
VdS: G213083
0786-CPR-21302
Selected voltage
230 V
115 V
X
X
Jumper X12
for AC 230 V
Jumper X11
for AC 115 V