background image

5

Siemens Industry, Inc. 5300 Triangle Parkway, Norcross, GA 30092

A5E32602904A-006

Accessories

Tamper Resistant Cover

Custom transparent cover may be sealed with wire seal to 

prevent unauthorized tampering with FLA adjustment dial, 

or DIP switch settings

.

49ASTC1

Reset Button Extender

Permits use with Siemens MCC’s and extra deep enclosures

       49ARES

Mounting Plate for ESP200

Starter size

Mounting Plate

      00-13/4

     49ASMP1

      2 - 21/2

     49ASMP2

           3 - 4 

     49ASMP3

Mounting Kit

The kit is used for remote mounting the ESP200 with fork 

terminal for wiring to contactors.

49ASMS1

49ASMS1

How to wire for Single Phase Motor

These ESP200 units below are specifically designed 

for single phase applications. 

 

 

 

 

3UB88134AB2    0.25 -1 Amps

3UB88134BB2    0.75 - 3.4 Amps

3UB88234CW2   3 -12 Amps

3UB88234DW2   5.5 -22 Amps

3UB88334GW2   25 -100 Amps

49ASTC1

Hazardous voltage.

Will cause death or serious injury

.

To avoid electrical shock or burn, turn off main and control

voltages before performing installation or maintenance.

T1

T2

L2

L1

TO SUPPLY

W

V

T1

T2

MOTOR

M

1

3

2

ESP200

5

9

6

9

A4- 97 98

A3+

GROUNDED BY

CUSTOMER

MAY BE

(OPTIONAL)

SEC FUSE

CONTROL FUSES

1

C

XF

H1

H4

H3

H2

B

X2

SEC

X1

CONTROL

TRANSFORMER

(OPTIONAL)

96

A

IF PROVIDED

Single Phase Magnetic Starter, Size 00–1

40ARES

49ASMP*

Fig. 10

Содержание ESP200

Страница 1: ...t in accordance with established safety practices b Is trained in the proper care and use of protective equipment such as rubber gloves hardhat safety glasses or faceshields flash clothing etc in accordance with established safety practices c Is trained in rendering first aid IMPORTANT THESE INSTRUCTIONS DO NOT PURPORT TO COVER ALL DETAILS OR VARIATIONS IN EQUIPMENT NOR TO PROVIDE FOR EVERY POSSIB...

Страница 2: ...ter Size 00 4 M 2 MOTOR T2 T1 T3 CONTROL DEVICE 3 TO PILOT W V 1 L1 L2 L3 TO SUPPLY IF PROVIDED ESP200 96 95 A4 97 98 A3 GROUNDED BY CUSTOMER MAY BE OPTIONAL SEC FUSE CONTROL FUSES 1 C XF H1 H4 H3 H2 B X2 SEC X1 CONTROL TRANSFORMER OPTIONAL 96 A Fig 6 4 Terminal Connections a b A B A A Coded A B A B 1 U 0 V 2 a b c d d c B B B Assembly Removal Remote Reset Connect 24 VDC to terminal A3 and A4 Auxi...

Страница 3: ...nnections and tighten to recommended torque Failure To Trip Out Possible cause Incorrect dial setting Action Readjust dial setting to the FLA on the motor nameplate Overload Trips Possible cause Motor is overloaded Action Remove cause of overload and reset overload relay Possible cause Loss of phase Action Replace burnt out fuse or reconnect wire in missing phase Possible cause Dial setting is too...

Страница 4: ...e ESP200 is activated by pressing the Exterior reset button mounted on the outside of the equipment enclosure When mounting the ESP200 inside an enclosure the External reset rod must first be cut to length Allow enough space between the External reset rod and the Blue reset button so that the Blue reset button is only activated when the External reset button is depressed ...

Страница 5: ...for wiring to contactors 49ASMS1 49ASMS1 How to wire for Single Phase Motor These ESP200 units below are specifically designed for single phase applications 3UB88134AB2 0 25 1 Amps 3UB88134BB2 0 75 3 4 Amps 3UB88234CW2 3 12 Amps 3UB88234DW2 5 5 22 Amps 3UB88334GW2 25 100 Amps 49ASTC1 Hazardous voltage Will cause death or serious injury To avoid electrical shock or burn turn off main and control vo...

Отзывы: