Technical data
ECOFAST Motor Starters
A-6
GWA 4NEB 950 5221-12 DS 01
A.1.5
Main power
A.1.6
Mechanical switching
Rated operating voltage
400 V AC
CLASS
10:
8 s
20:
16 s
30:
24 s
as per
4 to 10 s
standard
6 to 20 s
9 to 30 s
Rated insulation voltage
500 V AC
as per IEC 60947-1
Rated impulse withstand
voltage
4 kV
as per IEC 60947-1
Safety separation
300 V AC
between auxiliary
and main power
Frequency
50/60 Hz
ON duration
100%
Short-circuit protection
Fusible link
am-16 A/500VAC / Ik=120kA
Utilization category
1
Device destroyed after short-
circuit
Operating voltage
3 AC 200 V(-10%) to 460 V (+10%)
Operating current
0.3 A to 9 A
0.3 A to 7.3 A
0.3 A to 6.7 A
Class 10
Class 20
Class 30
Switching capacity
AC 3:
9.0 A
AC 4:
6.5 A
Switching load
3-phase
with SIMICONT contactor
Short circuit protection
Fusible link
am-16 A/500 VAC
I
Cu
= 120 kA
Lifetime of switching element
0.4 x 10
6
when I
e
= 9.0 A
1.1 x 10
6
when I
e
= 4.5 A
2.5 x 10
6
when I
e
= 3.0 A
7.0 x 10
6
when I
e
= 1.5 A
Approx. no. of operating
cycles per direction at 500 V
AC
Waiting time
The time between the switch-off command and the next
switch-on command
Motor CCW
Motor CW
OFF
300 ms
Содержание Ecofast 3RK1 323-2AS54-1AA0
Страница 1: ...Motor Starter Manual 03 2007 ecofast Totally Integrated Automation ...
Страница 2: ......
Страница 12: ...ECOFAST Motor Starters viii GWA 4NEB 950 5221 12 DS 01 ...
Страница 40: ...Installation of Motor Starters ECOFAST Motor Starters 3 8 GWA 4NEB 950 5221 12 DS 01 ...
Страница 58: ...Device functions ECOFAST Motor Starters 6 6 GWA 4NEB 950 5221 12 DS 01 ...
Страница 74: ...ECOFAST Motor Starters GWA 4NEB 950 5221 12 DS 01 ...
Страница 75: ......