Страница 1: ...ding on the loop The DLC communicates all relevant device and event information such as alarms and troubles to the System CPU The sensitivity of any intelligent smoke detector and the logic functions of any intelligent output devices can be checked and adjusted from the Operator Interface OI through the DLC All information about the devices on the loop can be displayed on the OI The DLC allows the...
Страница 2: ...d indicates that the DLC has detected an alarm TROUBLE Yellow Normally OFF When illuminated indi cates that the DLC has detected a trouble on its field wiring or incapability between firmware in either the OI DLC or both Multi Criteria detectors Table 1 are supported by the OI FW version 9 02 and later and the DLC with Firmware version 06 xx and later The DLC can be made backwards compatible in sy...
Страница 3: ...LASS A OPEN ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 wire is open if the loop was set to Class A CLASS A RETURN ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 return wire is reversed if the loop was set to Class A SHORT ZONE 2 Yellow Normally Off When illuminated indi cates a Zone 2 wire short Three rotary dial switches at the bottom of the front panel are u...
Страница 4: ...el is legible Slide the card in until the card edge connectors contact the receptacles on the motherboard Verify that the DIN connectors of the card and the card cage are aligned properly The card can only be plugged into the card cage in one direction if it does not align DO NOT FORCE the card Place thumbs on the front panel adjacent to the captive screws and gently apply even pressure on the car...
Страница 5: ...RUN OPERATES IN FULL CONFORMANCE WITH STYLE 6 ULC DCLA ZONE 1 ZONE 1 INITIATING DEVICE INITIATING DEVICE CC 5 CC 5 LINE 1 LINE 1 LINE 1 RETURN LINE 1 RETURN LINE 1 OUT LINE 1 OUT ZONE 2 ZONE 2 LINE 2 LINE 2 LINE 2 OUT LINE 2 OUT LINE 2 RETURN LINE 2 RETURN NOT USED NOT USED NOT USED NOT USED OPERATES IN FULL CONFORMANCE WITH STYLE 4 ULC DCLB SHIELD OPTIONAL TERMINATE IN ENCLOSURE WITH THE DLC TERM...
Страница 6: ... not allowed on Class A loops 7 All models are UL and ULC listed 8 The Multi Criteria detectors are programmed using the DPU The SBGA 34 base connected to a ZIC 4A P N 500 033050 or ZIC 8B P N 500 648670 can be used to createTemporal 4 tones in conjunction with the Carbon Monoxide enabled detectors FDOOTC441 and OOHC941 Using these detectors with the ABHW 4S or ABHW 4B the selection of tones are c...
Страница 7: ... 1 4 9 H O O 1 4 9 C H O O 1 2 9 P O C H L R W H L R 4 3 A G B S 7 8 5 5 0 4 0 1 V 6 A N P 7 8 5 5 0 4 0 1 V 6 A N P 8 8 5 5 0 4 0 1 V 6 A N P 9 5 6 5 9 0 5 1 3 N P 8 0 7 9 4 0 5 1 3 N P 0 1 2 3 3 0 5 1 3 N P 0 8 2 3 3 0 5 1 3 N P 3 9 1 4 9 0 5 1 3 N P 0 2 2 3 3 0 5 1 3 N P 6 6 8 6 3 3 0 1 V 6 A N P 6 6 8 6 3 3 0 1 V 6 A N P 2 6 6 4 2 3 0 1 V 6 A N P 6 2 9 3 2 3 0 1 V 6 A N P 5 5 6 4 2 3 0 1 V 6 A...
Страница 8: ...180 220 80 240 210 70 200 60 180 50 170 170 230 40 160 160 220 190 100 30 150 Note 1 The total number of devices in two zones can not exceed 252 150 210 90 200 80 DLC LINE RESISTANCE vs MAX CURRENT LOAD OF DEVICES 190 70 140 Max Current Load of Devices Line Resistance Ohms 60 130 50 110 120 140 20 250 Note 2 The total current load in two zones cannot exceed 350ma Note 3 Max line resistance of each...
Страница 9: ...eeds Such a security concept may result in additional site specific preven tive action to ensure that the building comfort fire safety security management or physical security system for your site are operated in a secure manner These measures may include but are not limited to separating networks physically protecting system components user awareness programs defense in depth etc For additional i...