28
Building Technologies
048_DMS_DF8000_ICC_MP4.15_A6V10081388_c_en.doc
Fire Safety & Security Products
06.2008
7.3
DF8045/46 front panel
Three dip-switches, located on the front panel of the DF8045/46 (refer to Fig. 24),
are used to set the module’s I
2
C address. Although there are 8 possible selections,
from 0 to 7, the valid I
2
C address can range from 0 to 2 (single unit) or 0 to 5 (dou-
ble unit). Refer to Annex B on page 36 for a complete list of the valid DF8000 con-
figurations.
Furthermore, 8 LEDs on the same front panel indicate the physical state of the in-
dividual inputs: the green LED is on when the input is in normal operation, the red
LED is on when an alarm condition is detected, in case of tamper (cable short or
open) both LEDs are on. These devices can be disabled from the CPU module to
reduce power requirements (see 4.1 and 10.4).
Fig. 24 DF8045/46 Front panel and external connections 1-8
Module
Address
Switch 1
Switch 2
Switch 3
Notes
0
Off
↓
Off
↓
Off
↓
1
st
module
1
On
↑
Off
↓
Off
↓
2
nd
module
2
Off
↓
On
↑
Off
↓
3
rd
module
3
On
↑
On
↑
Off
↓
4
th
module
4
Off
↓
Off
↓
On
↑
5
th
module
5
On
↑
Off
↓
On
↑
6
th
module
Tab.16. DF8045/46 Module Address settings
EMI filters on the DF8045/46 are dimensioned for the documented power supply
ratings.
Max input voltage
33 VDC
Max forward current
7 mA at 33 VDC
Tab.17. DF8045/46 max. ratings
7.4
DF8045/46 module mechanical dimensions
Width 45
mm
Height 75
mm
Depth 48
mm
Tab.18. DF8045/46 mechanical dimensions
I²C connector to
I/O modules
LEDs reporting status of inputs:
–
Left LEDs (Green): Normal
–
Right LEDs (Red): Alarm
–
Both / None: Tamper
Dip-switches for
address selection (1...6)
I²C connector to I/O
modules or CPU module
9
10
11
12
13
14
15
16
8
7
6
5
4
3
2
1
1
DF8045
1
2
3
4
ALARM
NORMAL
TAMPER
Содержание DF8000
Страница 4: ......
Страница 13: ...9 Building Technologies 048_DMS_DF8000_ICC_MP4 15_A6V10081388_c_en doc Fire Safety Security Products 06 2008 ...
Страница 45: ......