CA2N3851en_02 / 12.01.2007 

RXT20.1 – Service terminal Building 

Technologies 

2/6  

 

 

The housing accommodates a printed circuit board, the function keys, LCD and a socket 
for the commissioning and service tool. 

 
 
 
 

Connecting cable 

 

Base plate 

 

Housing 

80444

 

 
 
 
 
 
 

80084

 

Socket for RXT10 commis-
sioning and service tool 

 
 

90044 A

Service -
Pin

Landis & Staefa

Error

Displays room unit status, “wink” function, error messages or additional 
information of the room unit 

Function key 1: Error message display 

Cursor: Controller status indication 

Function key 2: Displays remote operation of service pin and additional 
information of the room unit  

 

Action Description 

Press + or – key 

Error

 

Press once to display any existing error messages. 

The error with the highest priority is displayed for 5 s. 

For error codes see “LCD display” 

 

Action Description 

Press left key 

Service
pin

 

The service pin is used to address the controllers when commis-
sioning the system. 
– RXC: refer to the RXT10 user manual, document CA2110338 
– RXB: refer to the ETS manual. 

This function of the service terminal is especially useful for ad-
dressing controllers in concealed locations where direct access to 
the service pin is difficult. For this purpose, the service terminal is 
connected to the room unit of the controller concerned. 

Press this key on the left side for at least 1.5 s for remote opera-
tion of the service pin of the connected DESIGO RXB / RXC con-
troller.  
While service-pin operation is in progress, the LCD display is 
blank. The controller, room unit and service terminal will then re-
start (ready for operation after approx. 3 – 5 minutes*) 

* Varies according to the DESIGO RX application  

Press right key 

 

1

st

 key press 

Room temperature display in °C 

2

nd

 key press 

Room temperature display in °F 

3

rd

 key press 

Setpoint adjustment display in °C 

4

th

 key press 

Setpoint adjustment display in °F 

5

th

 key press 

Return to original display (e.g. “run”) 

 

 

Elements for operation 
and display 

Function key 1: 

Function key 2: 

Содержание DESIGO RXT20.1

Страница 1: ...gated or into the room unit of the controller concerned The service terminal displays the status of the controller and room unit the wink func tion error messages or additional information of the room unit The service pin of the connected DESIGO RXB RXC controller can be operated re motely with the function keys on the service terminal This function is especially useful for addressing controllers ...

Страница 2: ...ess the controllers when commis sioning the system RXC refer to the RXT10 user manual document CA2110338 RXB refer to the ETS manual This function of the service terminal is especially useful for ad dressing controllers in concealed locations where direct access to the service pin is difficult For this purpose the service terminal is connected to the room unit of the controller concerned Press thi...

Страница 3: ...ields There is no room unit connected or the controller is not ready for operation but the power supply is working controller in start up phase or no application loaded or controller not configured Faulty controller No display The power supply is not connected or the controller is faulty Display Description Wink command Controller type displayed for 64 s e g RXC30 1 r 30 or RXB21 1 r 21 Press the ...

Страница 4: ... perature sensor of the connected room unit Display Description Room temperature in C or F see Function key 2 The displayed room temperature is the temperature measured by the room unit there is no temperature sensor in the service terminal itself The service terminal must have the same PPS2 address as the room unit address 1 12 in order to display any of the information described above The QAX3 r...

Страница 5: ...able length Approx 15 cm Housing protection standard Protection standard to EN 60529 IP 30 Protection class Insulation protection class III Environmental conditions Operation IEC 721 Climatic conditions Class 3K5 Temperature 0 50 C Humidity 85 rh Mechanical conditions Class 3M1 Transport IEC 721 Climatic conditions Class 2K3 Temperature 25 70 C Humidity 95 rh Mechanical conditions Class 2M2 Indust...

Страница 6: ...ommunicates with the controller via the PPS2 interface Addition ally the bus is looped through the service terminal RXC this enables a PC for the RXT10 service tool to be connected to the tool socket of the service terminal For correct operation of the service terminal there must always be a room unit connected to the controller PPS2 communication is not possible without a room unit 1 2 80443 A Au...

Отзывы: