EIA-485 interfaces 

Interface type 

EIA-485, electrically isolated 

Baud rate 

1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 
(depending on the configuration) 

Internal bus termination 

120 Ohm, switchable with DIP switch 

Internal bus polarization 

270 Ohm pull-up/pull-down resistances, switchable with 
DIP switch 

Cabling (in-house cabling only) 

Cable length 

3-wire cable 

Max. 1000 m (3300 ft) 

Protection 

Short-circuit proof 

Protection against faulty wiring with AC 24 V and 
DC 24 V 

 

 

USB interface (4G internet connection) 

Plug 

Type A 

Interface type 

USB 2.0 

Bit rate 

480 Mbit 

Max. load 

500 mA 

Max. cable length 

5 m 

 

Conformity 

 

Ambient conditions and protection classification 

Classification as per EN 60730 

Automatic action 

Control function 

Degree of pollution 

Overvoltage category 

 

Type 1 

Class A 

III 

Design 

Suitable for use in protection class I or II systems 

Degree of protection of housing to EN 60529 

Front parts in DIN cut-out 

Terminal part 

 

IP30 

IP20 

Climatic ambient conditions 
● 

Storage / Transport (packaged for transport) as per 
IEC EN 60721-3-1 / IEC EN 60721-3-2 
 

● 

Operation as per IEC/EN 60721-3-3 

 

 
● 

Class 1K22 / 2K12 
Temperature -25...70 °C (-13...158 °F) 
Air humidity 5...95 % (non-condensing) 

● 

Class 3K23 
Temperature -5...50 °C (23...122 °F)  
(for details see chapter Mounting) 
Air humidity 5...95 % (non-condensing) 

Mechanical ambient conditions 
● 

Transport per IEC/EN 60721-3-2 

● 

Operation as per IEC/EN 60721-3-3 

 
● 

Class 2M4 

● 

Class 3M11 

 

Содержание CXG3.X200

Страница 1: ...aces USB interface for 4G dongles Operating voltage AC 24 V or DC 24 V Mounting on standard rails or on the wall Plug in screw terminal blocks Multi site management depending on firmware Remote operation monitoring depending on firmware Alarm treatment depending on firmware Remote tool access update and configuration via Siemens Cloud Services de pending on firmware A6V11974867_en _b Smart Infrast...

Страница 2: ... trolled monitored devices such as controllers sensors and actuators in the building The device integrates common BACnet IP or Modbus TCP devices and systems as well as Siemens fire system protocols It securely transmits data to the cloud over cable networks or over mobile networks e g 4G With a router 4G USB Dongle support is available in addition see Accessories Type summary Type Order number De...

Страница 3: ... 3 Green Continuously ON Continuously OFF Flashing Link active No connection Network traffic Yellow Continuously ON Continuously OFF Link 100 Mbps Link 10 Mbps RUN Green Continuously ON Continuously OFF Flashing Device operational Device not operational Start up or program halted Red Continuously OFF Continuously ON Rapid flashing OK HW or SW fault power off and on the X200 Firmware or application...

Страница 4: ...fety regulations may result in personal injury and property damage Observe national provisions and comply with the appropriate safety regulations Mounting position and ambient temperature The devices can be snapped onto standard rails or screwed onto a flat surface Plug in screw terminals connect power and interfaces except for Ethernet Ambient temperature 5 50 C 23 122 F Ambient temperature 5 45 ...

Страница 5: ... a 4G dongle Reboot the device after a 4G dongle has been connected For details see 4G Dongle Setup A6V12059208 Disposal The device is considered an electronic device for disposal in accordance with European Directive and may not be disposed of as domestic waste Use only designated channels for disposing the devices Comply with all local and currently applicable laws and regulations Technical data...

Страница 6: ...ower failure Super cap to support real time clock 7 days Interfaces Ethernet interfaces Plug 3 x RJ45 shielded Interface type 10Base T 100Base TX IEEE 802 3 compatible Bit rate 10 100 Mbps autosensing Protocol BACnet on UDP IP and HTTPs on TCP IP Cabling cable type 10 Mbps Min CAT3 shielded cable is recommended 100 Mbps Min CAT5 shielded cable is recommended Cable length Max 100 m 330 ft Screw ter...

Страница 7: ...x load 500 mA Max cable length 5 m Conformity Ambient conditions and protection classification Classification as per EN 60730 Automatic action Control function Degree of pollution Overvoltage category Type 1 Class A 2 III Design Suitable for use in protection class I or II systems Degree of protection of housing to EN 60529 Front parts in DIN cut out Terminal part IP30 IP20 Climatic ambient condit...

Страница 8: ... accord ance with the instructions may cause harmful interference to radio communications Howev er there is no guarantee that interference will not occur in a particular installation If this equipment does cause harmful interference to radio or television reception which can be de termined by turning the equipment off and on the user is encouraged to try to correct the in terference by one or more...

Страница 9: ...stallation side with the building grounding system PE USB USB interface for 4G dongles Term on off Switch for bus termination Polar on off Switch for polarization 65 66 67 COM1 Interfaces EIA 485 68 69 70 COM2 Warranty Technical data on specific applications are valid only together with Siemens products listed under Equipment combinations Siemens rejects any and all warranties in the event that th...

Страница 10: ... A6V11974867_en _b Smart Infrastructure 2021 08 30 124 4 88 117 4 61 110 4 33 129 5 08 4 1 0 1 6 144 5 67 26 5 1 04 45 1 77 69 5 2 73 74 5 2 93 4 0 16 21 5 0 85 11 0 43 45 1 77 21 5 0 85 11 0 43 35 5 1 40 49 1 91 ...

Страница 11: ......

Страница 12: ... Global Headquarters Theilerstrasse 1a CH 6300 Zug 41 58 724 2424 www siemens com buildingtechnologies Siemens Switzerland Ltd 2021 Technical specifications and availability subject to change without notice Document ID A6V11974867_en _b Edition 2021 08 30 ...

Отзывы: