Siemens CSAPELTU Скачать руководство пользователя страница 2

2 / 4

Option: Circuit Breaker connected to system

When a Circuit Breaker is connected to the system and the Line Power is ON, use the Communications Adapter, Cat. No. CSAPELTU.  

1. Turn the circuit breaker to the OFF position as shown in step 3A. 
2. Connect the Communications Adapter to the circuit breaker as shown in step 3B.  
3. Turn the circuit breaker to the ON position so current is flowing through the circuit breaker as shown in step 3C. ( > 20%  

I

n )  

4. Power up the Laptop computer and start the SENTRON Viewer  software. See following pages for software use.
5. Turn Circuit Breaker OFF before disconnecting Communications Adapter from Circuit Breaker.

If the Circuit Breaker is disconnected from the system and bench tested, the Portable Test Set, Cat No. ELTPHB, can be used to power the Trip 
Unit by turning the “Trip Unit Active” power switch ON.  

Option: Circuit Breaker disconnected from system

Portable Test Set
(ELTPHB
3VL9000-8AK01  )                   

ON  /  I

D

C

ON  /  I

OFF / 0

A

ON / 1

C

B

B

3

Содержание CSAPELTU

Страница 1: ...se Danger de mort ou risque de blessures graves Hazardous Voltage Will cause death or serious injury Desenergice totalmente antes de instalar o darle servicio Reemplace todas las barreras y cubiertas antes de energizar el interruptor Turn off and lock out all power supplying this device before working on this device Replace all covers before power supplying this device is turned on Couper l alimen...

Страница 2: ...is flowing through the circuit breaker as shown in step 3C 20 In 4 Power up the Laptop computer and start the SENTRON Viewer software See following pages for software use 5 Turn Circuit Breaker OFF before disconnecting Communications Adapter from Circuit Breaker If the Circuit Breaker is disconnected from the system and bench tested the Portable Test Set Cat No ELTPHB can be used to power the Trip...

Страница 3: ...ct the Communications Adapter by starting over at step 2 Turn off and lock out all power supplying this device before working on this device Replace all covers before power supplying this device is turned on Couper l alimentation de l appareil et barrer avant de travailler Remplacez touts les couverts avant que l approvisionnement de pouvoir soit alimenté Tensión peligrosa Puede causar la muerte o...

Страница 4: ...ll 3 phases and neutral currents are graphed together The Help file is available with definitions for all the items on the program screen To start the help file system Click on the Help Button With the new cursor point at the item you need defined Click on that item and the appropriate help screen will be displayed 11 4 4 Subject to change without prior notice Siemens Energy Automation Inc 2006 Si...