S7-300 Automation System, Hardware and Installation: CPU 31xC and CPU 31x
A5E00105492-03
5-41
6WXEFDEOHV
If bus nodes are connected to a bus segment via stub cables (e.g. PG via a normal
PG cable), then you must consider the maximum possible length of the stub cable.
You can use a PROFIBUS bus cable with bus connector as the stub cable for up to
3 Mbps.
Use the patch cord to connect the PG or PC when operating above 3 Mbps. In your
bus configuration you can use multiple PG patch cords with this order no. Do not
use other types of stub cable.
7KHPD[LPXPFDEOHOHQJWKVIRU3*SDWFKFRUGV
... can be found in the Chapter
&DEOHOHQJWKV
.
&DEOH/HQJWK
03,VXEQHWVHJPHQW
You can implement cable lengths of up to 50 m in an MPI subnet segment. This
50 m applies from the first node to the last node in the segment.
Table 5-24
Permitted cable lengths in an MPI subnet segment
7UDQVPLVVLRQUDWH
6&38VQRQLVRODWHG
03,LQWHUIDFHZLWKRXW&38
'3
&38'3
19.2 kbps
187.5 kbps
50 m
1,000 m
1.5 Mbps
M 200
3.0 Mbps
6.0 Mbps
12.0 Mbps
-
M 100
6HJPHQWLQWKH352),%86VXEQHW
The cable length in a segment of a PROFIBUS subnet depends on the
transmission rate.
Table 5-25
Permitted cable lengths in a PROFIBUS subnet segment
7UDQVPLVVLRQUDWH
0D[LPXPFDEOHOHQJWKLQDVHJPHQW
9.6 kbps to 187.5 kbps
1,000 m
500 kbps
M 400
1.5 Mbps
M 200
3 Mbps to 12 Mbps
M 100
Содержание CPU 312
Страница 10: ... RQWHQWV S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x x A5E00105492 03 ...
Страница 76: ... RQILJXULQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 5 50 A5E00105492 03 ...
Страница 146: ... RPPLVVLRQLQJ S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 9 34 A5E00105492 03 ...
Страница 232: ... ORVVDU S7 300 Automation System Hardware and Installation CPU 31xC and CPU 31x 13 16 A5E00105492 03 ...